7.2 IEEE Curves
The SILA relay complies with the curves shown in standard IEEE:
•
Inverse Curve
•
Very Inverse Curve
•
Extremely Inverse Curve
There is a general mathematical equation that defines the time in seconds as a function of the current:
( )
+
−
=
B
V
A
TD
t
P
1
Where:
adjusted
I
I
V
=
Parameters
A
P
B
Ext. Inverse
28.2
2.00
0.1217
Very Inverse
19.61
2.00
0.491
Inverse
0.0515
0.02
0.114
The curve can move from its axis using the TD time selection device, which the user can adjust.
I
adjusted
is the initial operating current, set by the user.