Rev.04
36/112
This function allows to monitor the status of the circuit breaker and to perform preventive maintenance.
The following statuses are associated with this function:
Function Status
Description
52
Startup
These are the different statuses of the circuit breaker
automatic control.
The function only is initialized on Start when the relay is switched on.
If the relay doesn’t lose power supply, the last state is maintained.
Error
Open
Opening Time
Opening Error
Closed
Closing Time
Closing Error
Configured number of Openings
Alarm
Activated if the counter that measures the number of openings exceeds
the
‘
Maximum number of openings
’
setting
Configured accumulated amperes
alarm (I2t Alarm)
Activated if the accumulated amps counter exceeds
‘
Maximum
Accumulated Amperes
’
setting
Configured number of openings in
a time frame alarm
Activated if the number of openings exceeds the setting in
‘
Maximum
Number of Repetitive Openings
’
during the time set in
‘
Time of Repetitive
Openings
‘
. It works like a time accumulator, to be active it needs to detect
openings within the range defined by these two settings.
Monitoring function of circuit breaker will be more difficult depending on the available circuit breaker
contacts, zero, only one (52a or 52b) or both (52a and 52b).
If
no breaker contacts
are used, the monitoring of the circuit breaker is made through the current
measurement. This is, if less than 0.8% of rated current is detected it is considered the breaker is open
and if more than 0.8% of rated current is available, it is considered the breaker is closed.
Содержание SIL-A A Series
Страница 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Страница 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Страница 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Страница 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Страница 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Страница 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Страница 34: ...www fanox com Rev 04 34 112 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 61: ...www fanox com Rev 04 61 112...
Страница 63: ...www fanox com Rev 04 63 112...
Страница 64: ...www fanox com Rev 04 64 112...
Страница 65: ...www fanox com Rev 04 65 112...
Страница 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...