Rev.04
85/112
BLINKING (different time on (T) and time off (T2))
To delete the configuration, SICOM or HMI can be used. Through SICOM it is necessary to remove the configured signals and send the new configuration to the
relay.
Through HMI, it is necessary to access to the output PGC or LED that is configured and press OK to visualize the configured signals. Being displaying the configured
options, hold reset key to delete them. After inserting the password, by pressing OK the action of removing the configured options is confirmed. It is necessary to
press RESET key as many times as signals are configured.
The configured signal will be activated the time set in “time up” parameter and will be switched off the time set in “period”
parameter less
the set in “time up” parameter:
Содержание SIL-A A Series
Страница 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Страница 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Страница 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Страница 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Страница 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Страница 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Страница 34: ...www fanox com Rev 04 34 112 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 61: ...www fanox com Rev 04 61 112...
Страница 63: ...www fanox com Rev 04 63 112...
Страница 64: ...www fanox com Rev 04 64 112...
Страница 65: ...www fanox com Rev 04 65 112...
Страница 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...