Rev.04
95/112
9.2 Thermal resistance
•
4 times rated current continously.
•
30 times rated current for 10 s.
•
100 times rated current for 1s.
9.3 Energizing quantities
9.3.1 Burden for current measuring input
Being the relay set to the secondary nominal current of 1 amp, the burden for current measuring inputs
is:
Specified Burden of current inputs:
<0.1 mVA (1 A) <0.5 mVA (5 A)
Measured burden of current inputs:
Phase: 0.013 mVA
Neutral: 0.324 mVA
Being the relay set to the secondary nominal current of 5 amperes, the burden for current measuring
inputs is:
Specified Burden of current inputs:
<0.5 mVA (5 A)
Measured burden of current inputs:
Phase: 0.013 mVA
Neutral: 0.331 mVA