The feeder and supply will trip their functions as they see the fault. Supply’s time of
operation is larger than feeder’s time, so the
feeder will trip but it will not be able to open
its breaker. The feeder will block the supply the adjusted time, but in this case, the time of
operation of the supply is larger that this blocking time, so the supply will trip once its time
of operation finishes since it can still see the fault.