Rev.04
92/112
Function 46 (*)
Curve Type: IEC 60255-151 and IEEE curves.
Curve type: IEC Standard Inverse, IEC Very Inverse, IEC Extremely Inverse, IEC Long Time
Inverse, IEC Short Time Inverse, IEEE Moderately Inverse, IEEE Very Inverse, IEEE Extremely,
Defined Time.
Time delay: 0.000 to 300.000 s (step 0.001 s)
Time Dial (TMS): 0.05 to 25.00 (step 0.01)
-
If Curve type IEC: 0.05 to 1.00 (step 0.01)
-
If Curve type IEEE: 0.10 to 25.00 (step 0.01)
Current Tap: 0.010 to 20.000 xIn (step 0.001 xIn)
Curve, activation level: 110%
Curve, deactivation level: 100%
Defined time, activation level: 100%
Defined time, deactivation level: 95%
Instantaneous deactivation
Timing accuracy for IEC and IEEE curves selection:
± 30 ms or ± 5% (greater of both).
Timing accuracy for defined time curve selection:
± 35 ms or ± 0.5% (greater of both)
Function 46BC (*)
Function enable: No/Alarm/Trip/
Current Tap: 15 to 100 % (step 1%)
Time delay: 0.030 to 300.000 s (step 0.001 s)
Activation level: 100%
Deactivation level: 95%
Timing accuracy: ±30 ms or ±0.5% (greater of both)
Function 37 (*)
Function enable: No/Alarm/Trip
Current tap: 0.010 to 30.000 xIn (step 0.001 xIn)
Minimum Level: 0.000 to 1.000 xIn (step 0.001 xIn)
Time delay: 0.060 to 300.000 s (step 0.001 s)
Activation level: 100%
Deactivation level: 105%
Instantaneous deactivation
Timing accuracy: ±30 ms or ±0.5% (greater of both)
Function 79 (*)
Number of recloses: 0 to 4 (step 1)
Reclose time 1, 2, 3, 4: 0.020 to 2000.000 s (step 0.001 s)
Hold Enable: No/Yes/No Time
Hold time: 0.000 to 2000.000 s (step 0.001 s)
Reset time: 0.000 to 2000.000 s (step 0.001 s)
Safe time: 0.020 to 2000.000 s (step 0.001 s)
Locking possibilities: pulse inputs, level inputs, commands.
Function 52 (*)
Maximum number of openings: 1 a 100,000 (step 1)
Maximum accumulated amperes: 1 to 100,000 M(A2) (step 1 M(A2))
Repetitive number of openings: 1 to 100,000 (step 1)
Time for repetitive number of openings: 1 to 300 min (step 1 min)
Maximum opening time: 0.020 to 300.000 s (step 0.001 s)
Maximum closing time: 0.020 to 300.000 s (step 0.001 s)
Function 74TCS (*)
Function enable: No/Yes
Time delay: 0.020 to 300.000 s (step 0.001 s)
Continuity in circuits A and B
Function 60CTS (*)
Function enable: No/Yes
Time delay: 0.020 to 300.000 s (step 0.001 s)
Open breaker activation and reset threshold: 0.8% In
Detection of the loss of one phase CT
Function 50BF (*)
Function enable: No/Yes
Time delay: 0.020 to 1.000 s (step 0.001 s)
Содержание SIL-A A Series
Страница 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Страница 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Страница 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Страница 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Страница 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Страница 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Страница 34: ...www fanox com Rev 04 34 112 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 61: ...www fanox com Rev 04 61 112...
Страница 63: ...www fanox com Rev 04 63 112...
Страница 64: ...www fanox com Rev 04 64 112...
Страница 65: ...www fanox com Rev 04 65 112...
Страница 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...