8
MONITORING AND CONTROL
8.1 Measurements
Three-phase currents (I-A, I-B and I-C), neutral current (I-N), zero sequence current (3I0)*, positive
sequence current (I-1)*, negative sequence current (I-2)*, negative/positive sequence current relation
(I2/I1)*, maximum current (Imax), second harmonic of each phase (I-A2H, I-B2H and I-C2H), total
harmonic distortion (THD-A, THD-B, THD-C) and thermal image (TI) are given as fundamental values
(DFT).
The accuracy of the phases and neutral measurements in SILA is ±2% in a band of ± 20% the nominal
current and ±4% or ±5 mA (greater of both) in the rest of the band.
In case of the second harmonics currents the relay shows the measurements in amperes (although the
function is set in percentage).
8.2 Alarms Panel
Once the alarms are activated according to their configurations, they can be all recognized at the same
time by holding RESET key from the Alarms Panel main screen.
Accessing to the Alarms Panel, the alarms can be recognized one by one.
Depending on the configuration, after the recognition action, the alarms can be still activated, or they
can be deactivated. In alarms panel menu, these features will be shown. Considering this behavior, the
possibilities for the alarms are:
ALARMS STATE
ALARM PANEL
ACTIVATED
Recognized
OK
Not Recognized
OK
DEACTIVATED
Recognized
(*)
Not Recognized
OK
(*) Once one alarm is deactivated and recognized, it will disappear from the Alarms Panel.
NOTE: If any LED/Alarm has a SRFF or a RSFF configured with the Reset Key as Reset reason, when
pressing Reset from standby screen
, the LED’s will be reset. However,
to recognize the alarms we shall
do it from alarms panel menu.
Содержание SIL-A A Series
Страница 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Страница 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Страница 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Страница 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Страница 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Страница 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Страница 34: ...www fanox com Rev 04 34 112 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 61: ...www fanox com Rev 04 61 112...
Страница 63: ...www fanox com Rev 04 63 112...
Страница 64: ...www fanox com Rev 04 64 112...
Страница 65: ...www fanox com Rev 04 65 112...
Страница 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...