The start of a new cycle is possible only after reset meter from the 
control panel by pressing the RESET button, or via an external 
reset input. To protect the system against accidental erasure state 
of the counter, a zero signal is activated only after three seconds 
after pressing the RESET button or give a signal to enter reset.

Behind of local meter which is reset after work the button RESET 
the system is equipped with a total count, which caunt  all pulses 
and reset in a cuse when get full or reset from main menu. To read 
the value of the total meter, press OK.

00029867

TOTAL:

OK

00000999

 

>>

Counter stores its current state after turning off the voltage. This 
means  that  after  you  re-enable  system  restore  is  fed  both  the 
meter and the total  meter, as well as the transmitter output.

ATTENTION!

Meter configuration is make by a control panel with a keyboard 
and display. Passing the programming mode the meter is done by 
pressing the MENU button.

PROGRAMMING

OK

RESET

RESET

 SAVED

 

MENU

 CONT.  DC

 CONT.  DC

 SIGNAL

 SIGNAL

 SIGNAL

 AC_50Hz

 SAVED
 AC_50Hz

OK

OK

p

q

After select a menu signal, press OK. Then, using the UP and 
DOWN buttons to select the appropriate type of signal and enter 
the selection with the OK button. Entered message is the record 
of the name stored measured signal. Exit menu without saving 
the changes implemented by pressing the RESET button.

ATTENTION!

Choosing the type of count input signal is also the choice of type 
signal for the  RESET input.

3. FiltrDC

FiltrDC  menu  is  used  to  define  the  parameters  of  the  internal 
digital filter. It can help reduce frequency counting pulses to the 
set value, and thus reduce the possibility of wrong work of system  
caused  by  interference,  such  as  by  contact  vibration  systems. 
Diagram  of  the  digital  filter  configuration  is  presented  in  the 
following picture:

00000999

 

>>

MENU

THRESHOLD

THRESHOLD

THRESHOLD

THRESHOLD

 

MENU

 

SIGNAL

SET ZERO

 

MENU

 

MENU

 

LANGUAGE

FiltrDC

 

MENU

RESET

MENU

p

q

OK

tTo  select  menu  use  buttons  UP  or  DOWN.  Pass  to  choosen 
menu is possible by pressing button OK. Return to main menu is  
make by pressing button RESET.

Menu of meter 

This   parameter determines the number of pulses which to be 
count in each cycle.

1. Threshold

After selected the menu Threshold, press OK. Meter goes into 
edit  mode,  and  the  digit  being  edited  is  indicated  by  pulsing 
cursor. Use the buttons UP and DOWN to set a value on an item 
number, then use the MENU button to move the cursor to the next 
digit. After setting all the required numbers, enter a new value by 
pressing the OK button.

The parameter changes are indicated by the message 

saved and 

given the value of the parameter.

 In edit mode, you can return by 

pressing the RESET button, which will result in the abandonment 
of the changes and return to main menu

RESET

OK

00012000

00012000

SAVED

MENU

p

q

+1

-1

"

MENU

OK

00000000

RESET

2. Signal (INPUT)

Menu  signal  determines  whether  to  implement  the  counter 
counting  pulses  of  DC  signals  or  signals  for  the  AC  (with  a 
maximum frequency of 50Hz). How to set the measured signal is 
presented in the following picture:

Содержание CLG-03

Страница 1: ...o reset the current cycle of meter The programming mode allows you to go back to the higher level menus If the RESET button is pressed while editing a parameter the program comes from the editing mode without saving changes OK FUNCTIONING Measurement of the duration of the high In this mode the user specifies a set value of time the meter counts all the time in which the input is given gates high ...

Страница 2: ...on or from the input signal is given zero Set value METER PULSES RESET JOINT ON START STOP START STOP SET VALUE METER PULSES RESET JOINT ON START STOP START STOP ATTENTION Meter retains its current state after turning off the power supply voltage This means that after re power the system restore all the settings are both meter and meter indication and relay output status Programming of meter Meter...

Страница 3: ...aved with the name of the selected parameter Proceedings in determining the time display format is as follows 1 By button MENU pass to main menu 2 By buttons UP and DOWN select item Menu Format and press OK 3 Then shows Menu Format included follow items Format 6min Format 10min By buttons UP and DOWN select correct option and press button OK Enter choosen option is indicated by disply message Save...

Страница 4: ...e 4 To exit the option to choose the language without any changes press the RESET button Menu Light This parameter allowsto specify a way of highlight a meter display You can set the highlight permanently highlight or highlighting only for 60 seconds after you press any button To determine how the highlight you need 1 Pass to menu by pressing a button MENU 2 By buttons UPor DOWN select Menu Light ...

Страница 5: ...authorised modifications are to be made in the relay otherwise the device may be damaged or malfunction which in turn may lead to damage of the protected engine and jeopardise its operators Should this warning be ignored the producer cannot be held responsible for any related events and is entitled to deem this warranty invalid in the case of any complaint External signal does not permanently remo...

Страница 6: ...tended for counting the number of working hours in automatic production processes or the number of device working hours which due to safety requirements and operation efficiency have limited overhaul life i e operational capacity that may notbeexceeded e g advancedpowerunits specialradioactivelamps etc ASSEMBLY FUNCTIONING CLG 13T meter is an electronic one way meter enabling the counting of worki...

Страница 7: ...non voltage type internal battery baterry life 5 years read input voltage 4 30V DC input RESET 4 30V DC display 6 characters h 6 7mm precision 1 1digit working temperature 10 40 C dimensions 48 24 52mm fixing hole 45 23mm TECHNICAL DATA U URESET Do not dispose of this device to a garbage bin with other unsorted waste In accordance with the Waste Electrical and Electronic Equipment Act any househol...

Страница 8: ... are intended for counting the number of working hours in automatic production processes or the number of device working hours which due to safety requirements and operation efficiency have limited overhaul life i e operational capacity that may not be exceeded e g advanced powerunits specialradioactivelamps etc CLG 14T meter is an electronic one way meter enabling the counting ofworkinghoursin0to...

Страница 9: ...terylife 5years counteriputvoltage 24VAC DC maximumcountigfrequency 200Hz RESETinput non voltagetype display 8characters h 6 7mm precision 1min working temperature 10 40 C dimensions 48 24 52mm 45 23mm fixing hole D141114 AC DC RESET 5 9 0 8 3 1 2 5 9 8 0 8 4 F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice phone fax 48 42 215 23 83 227 09 71 POLAND http www fif com pl e mail fif fif com...

Страница 10: ...0V AC DC 1 Disconnectthepowersupply 2 Slidethemountingbracketofffromthebodyofthecounter 3 Put the counter into the mounting hole insert the fastening metalplateandtightenthenut 4 Connect the L N voltage which is an indication of the controlled device operation to the terminals of the counting input D160309 L N Purpose Functioning WARRANTY The F F products are covered by a warranty of the 24 months...

Страница 11: ...the casing front panel control It consists of a two lines eight alphanumeric display and placed under it keyboard with five buttons 01304569 TOTAL Two lineseight alphanumeric display Control buttons CLI 01 RESET OK MENU p q Display present information about the current state of work and in programming mode allows the configuration of the meter parameters The buttons on the control panel perform th...

Страница 12: ...e of type signal for the RESET input 3 FiltrDC FiltrDC menu is used to define the parameters of the internal digital filter It can help reduce frequency counting pulses to the set value and thus reduce the possibility of wrong work of system caused by interference such as by contact vibration systems Diagram of the digital filter configuration is presented in the following picture 00000999 MENU TH...

Страница 13: ...s is possible by press the RESET button Filtr NO Filtr 2Hz Filtr 5Hz SAVED xxxxHz Filtr 500Hz Filtr 1000Hz RESET p q FiltrDC MENU OK OK After you select a menu FiltrDC press OK Then using the UP and DOWN buttons to select the appropriate frequency filtering and approve it OK Exit menu without saving changes is possible by pressing the RESET button Set the menu item in FiltrDC doesn t mean exclusio...

Страница 14: ...for counting AC DC voltage signals generated by additional peripheral devices in order to determine the number of carriedoutworkingcyclesinautomaticssystems e g inordertocontrol the number of press strokes the number of revolutions of a rotating device thenumberofcomponentsleavingtheproductionline etc Assembly Functioning CLI 11T meter is an electronic one way meter enabling the counting of pulses...

Страница 15: ...ry battery life 5 years read input voltage 110 240V AC DC max coting frequency 200Hz input RESET non voltage type display 8 characters h 6 7mm precision 1 1digit working temperature 10 40 C dimensions 48 24 52mm fixing hole 45 23mm TECHNICAL DATA U URESET 5 9 0 8 3 1 2 5 9 1 8 4 9 F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice phone fax 48 42 215 23 83 227 09 71 POLAND http www fif com...

Отзывы: