The gate operator control board has a Fault Light to help determine fault shutdowns.  If the operator is not functioning properly, 
remove the cover and check the Fault Light for the operator Fault Status.  Use the following chart to determine the Fault: 

Number of 

Blinks 

Fault Description 

Sensitivity/Current 
Overload: 
Second Time 

Run Time Fault 

Sensor Fault/Failure 

PCB Overheat Fault 

Master Slave Fault 

Sensitivity/Current 
Overload: 
First Time 

Cause & Action 

Operator detected an unexpected current overload while moving. Usually caused 
by the gate hitting an obstruction or tripping the sensitivity.  This will put the 
operator in a Soft Shutdown. 
1. Make sure the sensitivity settings are set correctly.  Too light of a setting will 

cause the gate to stop and fault. 

2. Make sure there are no external obstructions that are causing the gate to stop 

and shutdown. 

Operator detected an unexpected current overload while moving a second time.  
Usually caused by the gate hitting an obstruction or tripping the sensitivity.  This will 
put the operator in a Hard Shutdown. 
1. Make sure the sensitivity settings are set correctly.  Too light of a setting will 

cause the gate to stop and fault. 

2. Make sure there are no external obstructions that are causing the gate to stop 

and shutdown. 

Operator has run longer than normal.  Usually caused by a bad limit or wiring fault . 
1. Check the limit for normal operation. 
2. Make sure the limit wire connections are tight.  

Motor Sensors have failed.  Usually caused by a bad sensor or loose sensor wire. 
1. Make sure the sensor wires are tight and well connected to the blue connector.  

While the operator is stopped, wiggle the Limit/Sensor connector.  If the limit or 
sensor wires blink on and off, there is a loose connection. 

2. Start the operator, watch Sensor 1 and Sensor 2 at startup.  They should both 

blink before turning solid.  If only one blinks, then the non-blinking sensor is not 
being seen. 

3. Remove the motor from the gearbox.  Both sensor lights should be on.  Pass a 

flat screw driver between Sensor 1 and Sensor 2 on the motor plate.  The 
Sensor LED on the control board should turn off and on as the screw driver 
passed through it. 

4. Make sure the sensor cup on the gearbox shaft is tight. A loose sensor cup will 

slip and cause the sensors to miss counts. 

Operator PCB has become too hot and caused a fault. 
1. Make sure the control board heat sink is secured to the side of the controller box 

to help dissipate excess heat. 

2. Determine if the operator has run excessively to cause an overheating problem. 
3. Possibly a defective heat sensor on the control board.  Have board repaired. 

Master Slave communication has failed.  Usually caused by a loose Master Slave 
wire or connector.  A very strong lightning strike can sometimes cause damage to 
the master slave circuit on the control board. 
1. Make sure the master slave wires are connected correctly and tight. 
2. Unplug the master slave wire and set both operators as Masters.  Test each 

operator independently to make sure there are no other problems or faults.  After 
determining each operator runs by itself, reset the master slave settings and 
connect the master slave wire.  If the problem continues, recheck wire and wire 
connections. 

3. Run a new CAT5 wire on top of the driveway to test the master slave 

communication.  This will determine if the underground wire is good or bad. 

4. 

Possible damage to the control board master slave components. Have boards 
repaired

FSW900 Swing Gate Operator 

27 

Содержание FSW900

Страница 1: ...nal Inc Headquarter East Coast Operations 5151 Sunbeam Road Suites 9 11 Jacksonville FL 32257 Tel 800 221 8278 www faacusa com FAAC International Inc West Coast Operations 357 South Acacia Avenue Unit...

Страница 2: ...Reverse Sensitivity Adjustment 16 Reverse Sensitivity Shutdown 16 Close Time Delay Adjustment 17 DIP Switch Settings 17 ACCESSORY CONNECTIONS Accessory Wire Overview 18 Edge Sensor Connections 19 Pho...

Страница 3: ...nderstand the manufacturer can not be held responsible for damage or injury caused by improper erroneous or unreasonable use Failure to comply with these guidelines may create a dangerous situation an...

Страница 4: ...ust be installed in a clear line of sight with the gate and its travel Activating devices must be installed a minimum of 10 feet away from the gate Be sure to mount ALL operating devices clearly out o...

Страница 5: ...nce some devices only cover a select area For example a photo beam will not cover the full height of a gate fence area Refer to the diagram below Contact Sensors Edge Sensors Contact sensors generally...

Страница 6: ...ion of a wall or fence system that controls entrance and or egress by people or vehicles and completes the perimeter of a defined area VEHICULAR SWING GATE OPERATOR Or System A vehicular gate operator...

Страница 7: ...d gate hardware before installing the gate operator Add safety devices such as warning signs photo eyes and reverse edges to help prevent injuries or death Reduce all pinch points and protect all entr...

Страница 8: ...p cover 3 Lift the Release Handle 4 Remove the Alignment Pin 5 Move the gate to the desired location To reengage the gate operator 1 Make sure power is OFF 2 Manually move the gate to align the arm wi...

Страница 9: ...er Input 120 VAC Current 6A Cycles Hour 75 Travel Speed 90 In Approx 14 Seconds Maximum Gate Weight 800 lbs Maximum Gate Length 18 Feet Primary Entrapment Protection Inherent Current Sensor Secondary...

Страница 10: ...ete pad terminating directly under the operator Extend each conduit a minimum of 1 above the level of the concrete pad See the Conduit Location diagram below It is suggested to install a minimum of fo...

Страница 11: ...ion 1 Make sure the Arm Operator and gate are level with each other 2 A Measure 46 from gate hinge out on gate 3 B Measure 35 5 for Long Arm length 4 C Measure 29 5 for Short Arm length 5 Use the Gate...

Страница 12: ...lose Limit Cams to the approximate location 2 Turn the operator ON and give it an open command Let it run until it gets to the open position Give the operator a stop command when the gate reaches the...

Страница 13: ...ied from a circuit breaker panel and must have its own dedicated circuit breaker This supply must include a green ground conductor 3 Only use UL approved 14 AWG or larger 600 Volt Insulated Wire Use t...

Страница 14: ...r DO NOT USE THESE POWER OUTLETS FOR INSTALLATION OR SERVICE TOOLS Each plug supplies 110 VAC when AC power is active to the gate operator If AC is not available the power plugs will not supply power...

Страница 15: ...Master and which operator is the slave All external devices such as loop detectors and safety devices must be wired directly to the Master unit If one gate travels further than the other the gate that...

Страница 16: ...the gate to stop the gate while in travel The gate should stop and enter a Soft Shutdown upon striking the object 10 Repeat steps 2 6 until the correct sensitivity adjustment is found REVERSE SENSITI...

Страница 17: ...Sounds the alarm in shutdown applications 2 Anti Tailgate OFF Gate opens and closes normal ON Uses loops to control vehicles individually 3 Master Slave OFF Operator is set as a Master Primary ON Ope...

Страница 18: ...TIONS ACCESSORY WIRE OVERVIEW CLOSE Photo Cell OPEN Photo Cell O P E N E D G E C L O S E E D G E Radio Receiver OPEN CLOSE STOP FIRE LOCK Card Access 1 2 3 4 5 6 7 8 9 0 Key Box 1 2 3 4 5 6 7 8 9 0 Ph...

Страница 19: ...reverse the gate to the full closed position and enter a soft shutdown 3 NOTE If the gate was initially activated by a time clock with a contact closure across the Access Input this input will be ign...

Страница 20: ...l be located where a risk of entrapment or obstruction exists such as the perimeter reachable by a moving gate or barrier and arm pinch point and entrapment areas Use caution when installing non conta...

Страница 21: ...to reset the operator settings Standard Reverse Input 1 Input is inactive when gate is closed or in the open cycle 2 When gate is open and Time Delay Close is ON an input will reset the Time Delay Cl...

Страница 22: ...ill remain open until an external input is made This prevents the Fire Input from closing the gate if in the open position Connecting Access Devices 1 Connect Fire Lock Control relays to FIRE and COMM...

Страница 23: ...the Radio Receiver uses 24VDC connect Radio Power to RADIO PWR 24VDC and RADIO PWR 24VDC Connecting FAAC XR2 Radio Receivers 1 Connect XR2 N O relay contacts to RADIO N O and RADIO COMMON 2 Connect X...

Страница 24: ...s are NO relay contacts Power must be applied externally Connecting External Alarm Warning Light 1 Connect Warning Light to the external power supply and Warning Com and N C outputs following the sche...

Страница 25: ...t should be 1 4 wide Cut diagonal corner slots to protect the wire insulation and keep the wire from changing directions quickly 3 Install loop wire Recommended Wire 14 AGW to 18 AGW Stranded XLPE Sta...

Страница 26: ...ket Make sure detector is secure and snapped in 4 Set different frequencies for each loop detector 5 Follow the directions provided with the PLD1500 for more detailed settings Ground Loop Wire Connect...

Страница 27: ...onnector While the operator is stopped wiggle the Limit Sensor connector If the limit or sensor wires blink on and off there is a loose connection 2 Start the operator watch Sensor 1 and Sensor 2 at s...

Страница 28: ...Controller PCB heat sink and faceplate assembly 3 GC 3000 Controller Assembly No PCB faceplate 4 MOTOR 0500 24 Motor 500W 24VDC 5 SW 0020 Gearbox 900 1 6 SW 0004 Weld arm connector with 12 bar 7 SW 00...

Страница 29: ...RE P PARTS ARTS Num FAAC p n Description 12 SW0003 Clutch assembly kit 13 SWITCH 0100 Limit switch 14 WIRE1101SK Sensors wire assembly with screws 15 AAA0450 Sensor cup assembly 16 AAA 0402 Motor Adap...

Страница 30: ...ability or reliability of the product s or has been subject to misuse negligence or accident or has not been operated in accordance with FAAC International Inc s instructions or has been operated unde...

Отзывы: