A1000
65
532210 04 - Rev.A
Tr
ansla
tion of the original instruc
tions
ENGLISH
Obstacle during opening
(number of obstacles =0)
If an obstacle is recognised during OPENING the doors stops moving
and after 10 seconds it attempts to reopen. Error 24 and then error
31 are generated when the programmed number of obstacles during
OPENING is reached.
The number of consecutive obstacles in opening is reset to zero:
-
with RESET command
-
upon reaching the OPEN position
-
by changing the operating mode.
-
An obstacle detected during opening in NIGHT-TIME function stops
the leaves and after the night-time pause time set they close again.
(safeties in closing and inputs not active)
14.5 ANTI-INTRUSION AND PULL&GO
The anti-intrusion is active when the door is manually moved from
the CLOSED position.
It is hindered during an attempt to open to return to the closed position
and signal 63 is activated.
The anti-intrusion is NOT active in NIGHT-TIME function with battery
operation.
The PULL&GO is active when the door is manually moved from the
CLOSED position to facilitate opening via activation of the motor.
The anti-intrusion is NOT active in PULL&GO function.
14.6 ELASTIC KIT
For the ELASTIC KIT parameter to be activated requires that the XDEK
anti-panic kit has been installed.
For installation and adjustment, refer to the specific instructions for
the XDEK .
Once installed, the XDEK allows the anti-panic opening of the leaves
in the event of a blackout.
14.7 ENERGY SAVING FUNCTION
The Energy Saving function allows you to decrease the opening/clos-
ing times and to limit the number of “false openings” by recognising
the pedestrian’s direction of movement with respect to the door (ap-
proaching, leaving, cross traffic).
This involves an opening movement by external or internal radars. It
reverses immediately when the radars are no longer engaged and the
presence sensors do not detect that anyone is present.
Obligatory requirements
The Energy Saving function requires:
the use of the one-direction radar detectors inside and outside
the operating mode to be AUTOMATIC.
!
To ensure maximum safety adhere to the detector’s operating instructions.
ACTIVATING THE ENERGY SAVING FUNCTION
In basic programming:
-
set
ES
ES
=
Y
Y
.
The parameter can be selected from the board or from the SDK EVO.
14.3 CONFIGURATION OF J22 OUTPUTS
01 and 02 specifications:
O1 Open Collector output with Max load 100mA to be connected
between 01 and V.
(Can be configured from the board and SDK EVO)
O2 relay contact with Max load 2A to be connected between O2
and O2.
(Can be configured from board and SDK EVO)
The OUT1 and OUT2 output signals may be configured as listed below:
Output DISABLED (no)
-
keeps the output always off.
Output configured as GONG(1)
-
activates and deactivates at 1 sec. intervals when the closing and
opening safeties are busy.
Output configured as ERROR(2)
-
activates the output when there is any active error or when an
intrusion is signalled during the night-time mode of operation.
Output configured as BATTERY(3)
-
the output is on when operation is with battery i.e. there has
been a power outage.
Output configured as EMERGENCY ACTIVE (4)
-
the output is on when an emergency is on.
Output configured as TEST (5)
-
activates the output to perform a test (FAIL SAFE) on the inputs
configured as closing and opening safeties on which the TEST
option has been activated before a closing or opening movement.
Output configured as DOOR NOT CLOSED(6)
-
the output is on when the door is in NOT CLOSED status.
Output configured as DOOR OPEN(7)
-
the output is on when the door is in open status.
Output configured as DOOR IN MOTION (8)
-
the output is on when the door is moving (opening or closing).
Output configured as LIGHT(9)
-
the output is on for a programmable time in NIGHT-TIME opera-
tion from leaf opening.
Output configured as INTRUSION(10)
-
the output is on when an intrusion is in progress (i.e. when the
encoder detects an unexpected movement of the door from the
closed position over 1 cm.)
Output configured as Safety in Closing (11).
-
activates the output when at least one Safety in Closing is On.
Output configured as Safety in Closing or Safety in Opening (12)
-
activates the output when at least one Safety in Closing or Safety
in Opening is On.
the output is on depending on how it has been programmed:
- normally open means the output contact closes when the output
is on
- normally closed means that the output contact opens when the
output is on.
14.4 OBSTACLE DETECTION
Obstacle during closing (
number of obstacles =0
)
The recognition of an obstacle during CLOSING causes the leaves
to reverse and the consecutive obstacles count during closing to
increase. The force and time parameters used by the motor when an
obstacle is detected can be selected.
Error 24 is generated when the programmed number of obstacles in
CLOSING is reached.
The number of consecutive obstacles during closing can be reset:
-
with RESET command
-
upon reaching the CLOSED position
-
by changing the operating mode
Содержание A1000
Страница 1: ...A1000 EN16005 2012 E1SL fw 3 0 SDK EVO fw 3 0 LK EVO fw 1 2...
Страница 108: ...A1000 108 53221004 Rev A Translation of the original instructions ENGLISH...
Страница 110: ...A1000 110 53221004 Rev A...
Страница 114: ...A1000 114 53221004 Rev A...
Страница 115: ...Translation of the original instructions ENGLISH...