35
EZ-TEXT-M-E
Text Panel Hardware Manual
PLC Messages and Local Messages
Embedded Data
The user message contains the ASCII
characters and optional embedded data
to be displayed. The embedded data
can be up to 3 different values —
DATA
1, DATA 2, and DATA 3.
Special characters in the message
determine where the embedded data
from the registers should go. When
programming, each character for
DATA
1
values will be represent by a “1” for up
to fi ve digits. For example, if you want
to display a fi ve digit value from the
PLC, you will press Ctrl + 1 or F5, fi ve
times, and “11111” will display in your
message (in red) representing the fi ve
digit value.
Only
DATA 1
’s embedded value can be
Interactive (READ/WRITE register)
,
meaning that data values will display and can be changed from the message.
DATA 2
and
DATA 3
are
Dynamic (READ ONLY register)
meaning that they
will display a value, but the value cannot be changed from the message.
DATA
2
values are entered into the message by pressing Ctrl +2 or F6, and are
represented by a “2” for each numeric digit, displayed in blue.
DATA 3
values
are entered into the message by pressing Ctrl +3 or F7, and are represented by
a “3” for each numeric digit, displayed in green. Again, these values can be up
to fi ve digits. Data values are only represented by a “1,” “2,” or “3” when you are
programming the message. The actual values will be displayed on the EZSeries
Set Point Display Text Panel LCD Display window, or will be blank if no value is
present. ( Password Protection is only available with EZSeries Set Point Display
Text Panel Models EZ-220P and EZ-220PV.)
For
DATA 1
, you can select a minimum and maximum range for the embedded
data value. The
Maximum
is to test for the upper limit for the data value and
Minimum
is to test for the lower limit for the data value. This will let the user update
the value between the ranges. Data values are incremented or decremented
with the
UP/DOWN Arrow
Buttons.
Also for
DATA 1
, you can choose to have the Decimal Point in the value controlled
by the PLC, or you can manually insert it in the message.
Please NOTE:
When selecting BCD
Data Type, only a 4-
digit value can be
used (0–9999).
Содержание EZ-220
Страница 27: ...23 EZ TEXT M E Text Panel Hardware Manual Connections and Wiring EZSeries Text Panel Application...
Страница 46: ...42 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Страница 65: ...61 EZ TEXT M E Text Panel Hardware Manual...
Страница 80: ...76 EZ TEXT M E Text Panel Hardware Manual...
Страница 81: ...77 EZ TEXT M E Text Panel Hardware Manual...
Страница 88: ...84 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Страница 100: ...96 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Страница 114: ...B 8 Text Panel Hardware Manual Omron C200 C500 RS 232 P N EZP OMRON CBL Siemens S7 MPI Adaptor P N EZP S7MPI CBL...
Страница 118: ...B 12 Text Panel Hardware Manual Idec MicroSMART PLC RS232 8 pin Mini DIN Male P N EZP IDECS CBL...
Страница 120: ...B 14 Text Panel Hardware Manual This page intentionally left blank...
Страница 150: ...I 8 EZ TEXT M Text Panel Hardware Manual This page intentionally left blank...