C-17
Text Panel Hardware Manual
Error T002: Invalid Access Type
Reason
: Access type of the specifi ed address is invald (e.g., entering a READ only address where a READ/
WRITE address type is expected.
Solution
: Supply the correct address.
Error T02_1: Invalid Unit Number.
Error T02_2: Invalid Address Type.
Error T02_3: Invalid Address.
Error T02_4: Invalid Bit Number.
Error T02_5: Address in not Word Aligned (Even address is required).
Error T02_6: Address is not Word Aligned (Odd address is required).
Reason
: Address entered for the PLC Address is not correct.
Solution
: Specify a valid PLC address.
Error T003: The value entered is invalid.
Reason
: The value entered for Minimum or Maximum fi eld is out of range.
Solution
: Supply values in the range 0…9999 for BCD and 0…65535 for Binary
Error T004: Unable to open tag map fi le : <fi lename> Please choose the map fi le
Error T005: Unable to open map fi le <map fi le>
Reason
: Think N Do map (.map) fi le not found.
Solution
: Locate the correct map fi le.
Error T006: Error in reading PLC Addresses
Reason
: Unable to generate PLC address while reading from the panel.
Solution
: Project in the Panel is corrupted. Reload the project to the panel.
Error T007: Unknown access type specifi ed for PLC Address.
Reason
: Invalid access type found while reading a project from disk.
Solution
: Project in the Panel is corrupted. Reload the project to the panel.
Message Error Messages:
Error M001: Unable to add a new Message/Folder. Possible cause: All the available 256
messages have been programmed
Solution
: Delete one or more messages or folders and try adding your message again.
Error M002: Invalid message number or this message number has already been confi gured.
Solution
: Please change the message number to a valid message number and ensure that this message
number was not programmed earlier.
Error M003: Cannot add a message with message number greater than 256.
Solution
: Message numbers have to be numbered with the range of 1 to 256. Please enter a valid
message number within this range.
Error M004: Invalid Message Number.
Solution
: Valid range for message number is 1 to 256. Please enter a valid message number.
Содержание EZ-220
Страница 27: ...23 EZ TEXT M E Text Panel Hardware Manual Connections and Wiring EZSeries Text Panel Application...
Страница 46: ...42 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Страница 65: ...61 EZ TEXT M E Text Panel Hardware Manual...
Страница 80: ...76 EZ TEXT M E Text Panel Hardware Manual...
Страница 81: ...77 EZ TEXT M E Text Panel Hardware Manual...
Страница 88: ...84 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Страница 100: ...96 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Страница 114: ...B 8 Text Panel Hardware Manual Omron C200 C500 RS 232 P N EZP OMRON CBL Siemens S7 MPI Adaptor P N EZP S7MPI CBL...
Страница 118: ...B 12 Text Panel Hardware Manual Idec MicroSMART PLC RS232 8 pin Mini DIN Male P N EZP IDECS CBL...
Страница 120: ...B 14 Text Panel Hardware Manual This page intentionally left blank...
Страница 150: ...I 8 EZ TEXT M Text Panel Hardware Manual This page intentionally left blank...