• The wall must be able to hold a load of at least 70 kg.
• Install the wall mount at a height of between 900 and 1200 mm above ground level.
4.1.4. Power supply requirements
DANGER:
Connecting the charging station to the power supply other than as specified in this section can
result in incompatibility of the installation as well as the risk of electric shock, and thus cause
damage to the charging station, and injury or death.
• Only connect the charging station to a power supply in a configuration that is specified in
this section.
Earthing
system
TN-system
PE-cable.
TT-system
IT-system
Earth electrode, installed separately.
Power input
(phase)
1-phase
230 V ±10% 50/60 Hz.
3-phase
400 V ± 10% 50/60 Hz.