8) Parameter group 100: Basic parameter
F124
Jog frequency (Hz)
Range: F112 - F111
Default setting: 5.00 Hz
F125
Accel. ramp
– Jog Mode (sec.)
Range:
Default setting: 0.2 - 3.7KW: 5.0 sec.
5.5 - 30KW: 30.0 sec.
F126
Decel. ramp
–Jog Mode (sec.)
0.1
– 3000 sec.
> 37
KW: 60.0 sec.
There are two modes to activate the Jog frequency: Keypad-control, and terminal-control (programmable digital inputs
DI1…DI6(8) – configuration:
F316…F323
).
Keypad-control:
With the inverter in STOP mode press
key, to display HF-0, in this condition the
key works as a
Jog frequency start/stop toggle (
F132
must be configured in the proper way
1
+x+x+x).
Terminal control:
A proper configured digital input works as Jog frequency start/stop toggle
Remark: In Jog mode the "catch on the fly" function is deactivated
F127/F129
Cut-Off frequency A,B (Hz)
Range: 0.00 - 650.0
Default setting: 0.00 Hz
F128/F130
Cut-Off frequency window A,B (Hz)
Range: ±2.5 Hz
Default setting: 0.0 Hz
Cut-Off frequency to avoid resonance problems
– the inverter transits during accel. / decel. ramps through this frequency areas,
but it can not stay stable within this frequency ranges.
Display configuration:
0:
Output frequency / parameter value
1:
Motor speed (rpm)
2:
Motor current
4:
Motor voltage
8:
DC-voltage
16:
PID control feed back
Default setting:
F131
Display: Selection of operating
32:
Heatsink temperature
0+1+2+4+8=15
parameters to display during „START“
64:
Counter
(fspeed+motor-
status (Motor running)
128: Speed (linear - calculated
motor-
256: PID set-point
DC-voltage)
512: Reserved
1024: Reseved
2048: Motor-Power
4096: Motor-Torque
8192: Reserved
To display a specific parameter, just set Parameter
F131
to one of the values in the table above, to display more
parameters, the sum of all values must be set in
F131
The
key is used to cycle through the various selected parameter values
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 36 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Содержание E2000-0004 S2B
Страница 14: ...2 Product data product power range E2000 _Rev 02 E SOFT Rev 5 09 12 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 72: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 75: ...17 Parameter group A00 PID controller setup E2000 _Rev 02 E SOFT Rev 5 09 65 2016 06 KPP EURADRIVES EUROPE GmbH...