11) Parameter group 400: Analog I/O configuration
11) Parameter group 400: Analogue I/O channel configuration
Two different control boards are used in E2000+ inverters, depending on inverter framesize:
Inverter power-range up to 22 kW - size E1-E6
Inverter power-range 30
– 400 kW - size C3-C6
Both control boards offers independent analogue input/output channels. Each of them can be adapted to
various input/output signals
– all configuration must be done by software/hardware setting
Details and instruction for hardware setting: see chapter
5) Control hardware and IO/ channel configuration
Following instruction describes, how to set software parameters
Configuration of analogue speed reference channels
AI1, AI2, AI3
(A3 = potentiometer on
keypad):
F400
Range definition
AI1
– lower limit (V)
Ra
nge 0.00V…F402
Default setting: 0.00V
F401
Assignation lower limit
AI1
Range: 0…F403
Default setting: 1.00
F402
Range definition
AI1
– upper limit (V)
Range: F400…10.00V
Default setting: 10.00V
F403
Assignation upper limit
AI1
Range: (1.00, F401)…2.00
Default setting: 2.00
F404
Gain factor
AI1
Range: 0.0…10.0
Default setting: 1.0
F405
AI1 Filter factor
AI1
Range: 0.1…10.0
Default setting: 0.10
The speed range is defined by upper and lower limits, the area in between corresponds to 100%
(example:
F400=2, F402=8, 2…8V correspond to 0....100%)
Parameter F401 and F403 are used to move the range limits (in %). Rules: 0 = -100%, 1 = 0%, 2 = +100%.
(example: F401=0, F403=2 then 100% signal (the range between upper and lower limit) correspond to -
100%...+100% reference). In this case 0...10V input signal corresponds to -
50 Hz…0Hz…+50 Hz).
A= (F401-1)*100%
B= (F403-1)*100%
C= F400
D= F402
Configuration examples:
Speed reference channel selected:
AI1 - F203=1
,
F-max:
F111=50 Hz
, F-min:
F112=0Hz
All other: default set
B
AI
1
A
C
D
Speed reference Output frequency
F400
F401
F402
F403
F404
Hardware setting
0..10V
0Hz...+50 Hz
0.00V
1.00
10.00V
2.00
1.0
0... 10V
0... 10V
-50Hz
....0Hz...
+50Hz
0.00V
0.00
10.00V
2.00
1.0
0... 10V
0... 10V
-50Hz.... 0Hz
0.00V
0.00
10.00V
1.00
1.0
0... 10V
0... 10V
20Hz.... 50 Hz
0.00V
1.40
10.00V
2.00
1.0
0... 10V
-10V...+10V
-50Hz... 0Hz... +50 Hz
0.00V
0.00
10.00V
2.00
1.0
+/-...
10V
0... 20mA
0Hz.... 50Hz
0.00V
1.00
10.00V
2.00
1.0
0... 20mA
4... 20mA
0Hz.... 50Hz
2.00V
1.00
10.00V
2.00
1.0
0... 20mA
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 49 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Содержание E2000-0004 S2B
Страница 14: ...2 Product data product power range E2000 _Rev 02 E SOFT Rev 5 09 12 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 72: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 75: ...17 Parameter group A00 PID controller setup E2000 _Rev 02 E SOFT Rev 5 09 65 2016 06 KPP EURADRIVES EUROPE GmbH...