16) Parameter group 900: RS485 hardware and interface parameters
16) Parametergroup 900: RS485 hardware and interface parameters
Please refer on specific MODBUS manual, for protocol, control algorithm, control registers, and other details
F900
Inverter adresss
Selection: 1…255: fixed adresses
Default setting: 1
0: adress set via BUS
F901
RS485 operation mode
Selection: 1: ASCII protocol
Default setting: 2
2: RTU protocol
F902
Number of STOP bit
Selection: 1 - 2
Default setting: 2
F903
Parity check
Selection 0: no check
Default setting: 0
1: ODD parity
2: EVEN parity
Selection: 0: 1200
1: 2400
2: 4800
Default setting: 3
F904
Baudrate
3: 9600
4: 19200
5: 8400
6: 57600
F905
MODBUS Time-out
Range: 0.0.....3000 sec.
Default: 0.0 sec
F907
M-BUS Time-out warning
Range: 0.0.....3000 sec.
Default: 0.0 sec
F905:
MODBUS time-out, in case of missing MODBUS command within the timeframe, set in
F905
inverter will STOP for
safety
reason and
CE
will appear on the display. For
F905=0
, the safety function is disabled.
F907:
MODBUS time-out warning. If
F907>0
, and MODBUS signal is missing for the time, set by
F907
, the inverter will send an
error warning trough a programmable digital output (mapping code
43
). This signal may be reset via digital input (mapping code
60
).
Hardware MODBUS - interface :
All EURA Drives inverter are equipped with a unique RS485 connector. This port is used for inverter control via
MODBUS and for parametrizing the inverter, using PC software or COPY STICK.
The picture below shows the pin-out of the 4 pole connector
An auxiliary power supply, based on microprocessor ground delivers 50 mA / 5V
Inverter up to 22 kW
Size E1 - E6
:
The interface connector is located on the left side of the inverter
Inverter 30 kW and above
Size C3
– C6
:
The interface connector is located on the controlboard inside the drive
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 63 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Содержание E2000-0004 S2B
Страница 14: ...2 Product data product power range E2000 _Rev 02 E SOFT Rev 5 09 12 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 72: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 75: ...17 Parameter group A00 PID controller setup E2000 _Rev 02 E SOFT Rev 5 09 65 2016 06 KPP EURADRIVES EUROPE GmbH...