17) Parameter group A00: PID controller setup
Emergency functions
+
FA59
Selection of different emergency
Selection: 0: no function selected
1: FIREMODE 1
Default setting: 0
functions
2: FIREMODE 2
FA60
Frequency for emergency condition
Range F112…F111
Default setting: 50 Hz
FA58
Pressure for emergency conditions
Range 0.0….100%
Default setting: 80%
FA62
Trigger mode
Selection: 0: no function selected
1: FIREMODE 1
Emergency condition is triggered through specific terminal command (digital input - DIx assignation code
33
) in this case, all
protection functions are deactivated, and all auto-restart functions are activated.
FIREMODE 1 Inverter works with the regular set-point
FIREMODE 2, Inverter works with fixed frequency, set in parameter
FA60
Emergency pressure mode is activated by terminal, digital input (DIxx assignation code
32
)
FA62=0:
Inverter stays in FIREMODE, once triggered by digital input,
FA62=1:
inverter quits from FIREMODE, after
trigger
input is disactivated.
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 67 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Содержание E2000-0004 S2B
Страница 14: ...2 Product data product power range E2000 _Rev 02 E SOFT Rev 5 09 12 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 72: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 75: ...17 Parameter group A00 PID controller setup E2000 _Rev 02 E SOFT Rev 5 09 65 2016 06 KPP EURADRIVES EUROPE GmbH...