4) Electrical connections of E2000+ inverters
Sample set-up for inverter 22 kW, 400V - framesize
E6
If parameter status is unknown, factory reset is recommended:
Set parameter
F160 = 1
Analogue speed reference 0....10V (potentiometer) through input channel
AI1
:
Set
F203=1
START/STOP command and inversion through terminal signals: set
F208=2
(two wire
control) Fault signalling on relays contact:
F300=1
(already default set)
„Inverter enabled“ message on
DO1
F301=14
(already default set)
Frequency indication output:
AO1
0…10V = 0-50 Hz
F423=1, F431=0
(already default set)
E2000+_Rev.02 -D- SOFT Rev. 5.09
- 23 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH