1) Common installation rules and safety information regarding EURA E2000+ inverters
Inverters with UL mark: Additional information
Following information are valid for inverters, designed for use in countries, which require UL approval.
All information below must be available to all who are responsible for commercialization, installation and place in
operation.
UL Standards
The UL/cUL mark applies to products in the United States and Canada and it means that UL has performed product testing and
evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all
components inside that product must also receive UL certification.
UL Standards Compliance
This drive has been tested in accordance with UL standard UL508C, File No. E363934 and complies with UL requirements. To
ensure continued compliance when using this drive in combination with other equipment, meet the following conditions:
1)Do not install the drive to an area greater than pollution severity 2 (UL standard)
2)Installation and operating instructions shall be provided with each device.
The following markings shall appear in one of the following locations: shipped separately with the device; on a separable, self-adhesive
permanent label that is shipped with the device; or anywhere on the device itself.
a)
Designation markings for each wiring diagram;
b)
Markings for proper wiring connections.
c)
“Maximum Surrounding Air Temperature 40ºC.” or equivalent;
d)
“Solid State motor overload protection reacts when reaches 150% of FLA” or equivalent;
e)
“Install device in pollution degree 2 environment.” or equivalent;
f)
For Models of Frame Size(E2000-0007T3UBR;E2000-0011T3 UBR;E2000-0015T3 UBR;E2000-0022T3UBR): “Suitable For Use On A
Circuit Capable Of Delivering Not More Than 5,000 rms Symmetrical Amperes, 480 Volts Maximum When Protected By made by
COOPER BUSSMANN L L C Class T Fuse: JJS-15.” or equivalent.
For Models of Frame Size (E2000-0030T3UBR;E2000-0037T3UBR;E2000-0040T3UBR): “Suitable For Use On A Circuit Capable Of
Delivering Not More Than 5,000 rms Symmetrical Amperes, 480 Volts Maximum When Protected By made by COOPER BUSSMANN L L C
Class T Fuse: JJS-25.” or equivalent.
For Models of Frame Size (E2000-0055T3UBR;E2000-0075T3UBR): “Suitable For Use On A Circuit Capable Of Delivering Not More Than
5,000 rms Symmetrical Amperes, 480 Volts Maximum When Protected By made by COOPER BUSSMANN L L C Class T Fuse: JJS-35.” or
equivalent..
g)
“Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in
accordance with the National Electrical Code and any additional local codes” or the equivalent;
h)
“CAUTION – Risk of Electric Shock” should be provided, followed by instructions to discharge the Bus Capacitor or indicating the
time required (5 minutes) for Bus Capacitor to discharge to a level below 50 Vdc;
i)
“Drives have no provision for motor over temperature protection” or equivalent;
j)
For used in Canada only: “TRANSIENT SURGE SUPPRESSION SHALL BE I NSTALLED ON THE LINE SIDE OF THIS
EQUIPMENT
AND SHALL BE RATED __480_ V (PHASE TO GROUND), 480 V (PHASE TO PHASE), SUITABLE FOR OVERVOLTAGE
CATEGORY _III_, AND SHALL PROVIDE PROTECTION FOR A RATED IMPULSE WITHSTAND VOLTAGE PEAK OF _6 kV” or
equivalent.
Field Wiring Terminal Markings – Wiring terminals shall be marked to indicate the proper connections for power supply and load, or a
wiring diagram coded to the terminal marking shall be securely attached to the device:
a.“
Use 60/75
°
C CU wire” or equivalent;
b.
Required wire torque, type and range listed: see chapter
4)
Empfohlene Leitungsquerschnitte
– Sicherungen Leistungsklemmen
Grounding – The wire connector intended for ground connection for field installed equipment, shall be clearily identified such as being
marked “G”, “GRD”, “Ground”, “Grounding”, or equivalent or with the grounding symbol (IEC 417, Symbol 5019).
Tightening torque and wire section for field grounding wiring are marked adjacent to the terminal or on the
EMV: Grundlagen und
ire section for field grounding wiring are marked adjacent to the terminal or on the wiring diagram.
E2000+_ Rev.02 -E- SOFT Rev. 5.09
- 10 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Содержание E2000-0004 S2B
Страница 14: ...2 Product data product power range E2000 _Rev 02 E SOFT Rev 5 09 12 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 72: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 75: ...17 Parameter group A00 PID controller setup E2000 _Rev 02 E SOFT Rev 5 09 65 2016 06 KPP EURADRIVES EUROPE GmbH...