18) Parameter group C00: Speed / Torque control
Speed limiting for inverter, working in torque control mode:
Selection: 0: Set by FC23
1: Analogue input AI1
FC22
Speed limiting set-point origin forward
2: Analogue input AI2
Default setting: 0
3: Analogue input AI3
4: Pulse signal input
5: Reserved
FC23
Internal speed limiting value forward
Range: 0...100 %
Default setting: 10%
Selection: 0: Set by FC25
FC24
Speed limiting set-point origin reverse
1: Analogue input AI1
Default setting: 0
2: Analogue input AI2
3: Analogue input AI3
FC25
Internal speed limiting value reverse
Range: 0...100 %
Default setting: 10%
(All values are referred to f-max
–F111)
Torque limiting for inverter working in speed control mode
Selection: 0: Set via FC30
1: Analogue input AI1
FC28
Torque limiting signal source motor mode
2: Analogue input AI2
Default setting: 0
3: Analogue input AI3
4: Pulse signal input
5: Reserved
FC29
Reference: 100% of limiting signal to motor
Range: 0,0....3,000
Default setting: 3,000
rated torque
FC30
Internal torque limiting value
Range: 0....300% %
Default setting: 200%
motor mode (%)
(All referred on motor rated torque)
Selection: 0: Set via FC35
1: Analogue input AI1
FC33
Torque limiting signal source generator mode
2: Analogue input AI2
Default setting: 0
3: Analogue input AI3
4: Pulse signal input
5: Reserved
FC34
Reference: 100% of limiting signal
Range: 0,0....3,000
Default setting: 3,000
to motor rated torque
FC35
Internal torque limiting value
Range: 0....300% %
Default setting: 200%
generator mode (%)
(All referred on motor rated torque)
+
Torque / Current limit for field wakening area
FC 48
Activation of secondary limiting
Selection: 0: Limiting fixed
Default setting: 0
1: Depending on frequency threshold
FC49
Sekundary torque/current limit (%)
Range: 50...200 %
Default setting: 120%
FC50
Start transition frequency (Hz)
Range: 1.0 Hz....FC51
Default setting: 15 Hz
FC51
End transition frequency (Hz)
Range: FC50...F111 Hz
Default setting: 30 Hz
In V/Hz mode: To limit motor current in the field wakening area
In SLV mode: To limit torque in the field wakening area
Current / Torque
FC608/30
FC49
FREQUENCY
F50
F51
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 69 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Содержание E2000-0004 S2B
Страница 14: ...2 Product data product power range E2000 _Rev 02 E SOFT Rev 5 09 12 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 72: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Страница 75: ...17 Parameter group A00 PID controller setup E2000 _Rev 02 E SOFT Rev 5 09 65 2016 06 KPP EURADRIVES EUROPE GmbH...