Installation
Wiring
A 3-wire shielded cable: 3-conductor, 18 AWG stranded
General Cable E2203S.30.860, or equivalent is recommended. The
maximum permissible cable length is 0.62 miles (1 km).
The OMS requires a single, 3-wire shielded cable for analog output and 24 VDC
power input. The analog out and VDC power in connections are made on the
terminal block inside the transmitter housing.
Pin#
Connection
Description
–
Common (Signal Ground)
0V
–
Common (Signal Ground)
0V
MA
Signal Out
DC 4–20 mA Output
+
Power
DC + 24 V Input
+
Power
DC + 24 V Input
Additional contacts for +24 VDC Power and Common have been added to
accommodate additional wiring for remote horns and strobes.