CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
47 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
6.2 All objects with channel A
6.2.1 Objects “Response”
NO Object name
Function
Flags
Data type
11 Output A
No response
/Always respond
/Only after
change
C R T
EIS1
DPT 1.001
1 bit
This communication object uses the channel A response status, if channel
status is ON, then the response status value is “1”, otherwise the status value
is “0”.
Table 4. Response
6.2.2 Objects “R/W statistics for time”
NO
Object name
Function
Flags
Data type
12
Output A
Read/write
statistics for
time
C R W T U
EIS10
DPT 7.007
2 bytes
This communication object is used for statistics ON-time of the channel “A”.
This communication object is used for alarm when ON-time out set range.