CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
18 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
Always respond: Always receive a response of the switch state when a channel
telegram data is received.
Only after change: Only receive a response of the switch state when channel
stateis changed.
Save statistic for ON switching “time(hour-2bytes)”
Statistics for channel ON time, useful for management and monitoring.
Options:
Disable
Enable
Disable: Disable statistics.
Enable: Enable statistics only for the ON time.
Alarm for time out
Options:
No
Yes
No: No alarm when time out.
Yes: Alarm.
Alarm when time out (1–65,535 h)
This parameter sets the ON time alarm overflow time.
Options:
1–65,535 h
Alarm telegram interval when time out (1–255 s)
This parameter sets the ON time overflow alarm interval.
Options:
1–255 s
Alarm telegram number (1–255, 0 – unlimited)
This parameter sets the number of telegram repetitions for the alarm.
Options:
0–unlimited
1–255
Save statistic for ON switching “counter (4bytes)”
Statistic channel switch ON counter
Options:
Disable
Enable
Disable: Disable Statistic ON counter
Enable: Enable Statistic ON counter
Alarm for counter out
Options:
No
Yes
No: No alarm
Yes: Alarm