CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
41 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
Disable: Disable logic connection 2
Enable: Enable logic connection 2
Function of logic block 2
This logic block allows selection of “AND” or “OR” or “XOR” or “GATE”
for Boolean calculation by user.
Options:
AND
OR
XOR
GATE
AND: Boolean calculation according to “AND” rule.
OR: Boolean calculation according to “OR” rule.
XOR: Boolean calculation according to “XOR” rule.
GATE: “Out” Keep state same as before when value of “Con2” set to 0.
Output of logic block 1 passes through to “Out” of logic block when value of
“Con2” set to 1.
Object value of logic connection 2 after bus voltage recovery
Set the value of logic connection 2 after bus voltage recovery.
Options:
0
1
0: Initialisation logic connection 2 value is 0.
1: Initialisation logic connection 2 value is 1.
Result of logic block 2 inverted
When setting this parameter to YES, the output of connection 2 will be inverted.
Options:
NO
YES
NO: Result of block not inverted.
YES: Result of block inverted.
5.6 Channel “Heating actuator”
PWM control
Type of control can be 1 bit or 1 byte.
1 bit PWM (1-start/0-stop): The PWM is switched ON by receiving then telegram
value “1”, and stopped by “0”.
1 byte (255-ON/0-OFF/other valve): Always switched ON by the receiving telegram
value of “255”, and switched OFF by the receiving telegram value “0”. The
PWM runs and pulse width of PWM is set according to the value of the receiving
telegram (1 to 254)