Modbus reading addresses 1-Wire Sensors
Reading addresses
Temperature-
and Humidity-
sensor
e.g. Art. No.
11131, 11132,
11134, 11135,
11150, 11160 and
further more
Temperature-,
Humidity- and Air
Quality-Sensor
e.g. 11151 and
11152
Temperature,
Brightness and
Solar Radiation
e.g. 11112
Brightness-
sensor
e.g. 11129
Note
Address
Number
of
words
(16Bit)
Type
of
data
Bit
address
1-Wire multisensors standard and PRO
OWD 1
40100
1
Integer
Temperature
Temperature
Not in use (255)
Not in use (255)
Temperature
40101,40102
2
Dword
1632 to
1639
(102*16)
Operating voltage
Operating voltage
Temperature
Status input
decimal
HH HL LH
LL
40103,40104
2
Dword
Humidity
Humidity
Operating voltage
Status input
binary
HH HL LH
LL
40105,40106
2
Dword
Dew point
Dew point
Brightness
Status output
decimal
HH HL LH
LL
40107,40108
2
Dword
Brightness
Brightness
Solar Radiation
Status output
binary
HH HL LH
LL
40109,40110
2
Dword
Not in use (255)
Air Quality
Not in use (255)
Not in use (255)
HH HL LH
LL
40111,40112
2
Dword
Status
Status
Status
Status
HH HL LH
LL
40113,40114
2
Dword
Error Counter
Error Counter
Error Counter
Error Counter
HH HL LH
LL
40115,40116
2
Dword
Article number /
Type
Article number /
Type
Article number /
Type
Article number /
Type
HH HL LH
LL
OWD 2
40200
1
Integer
Temperature
Temperature
Not in use (255)
Not in use (255)
Temperature
40201,40202
2
Dword
3232 to
3239
(202*16)
Operating voltage
Operating voltage
Temperature
Status input
decimal
HH HL LH
LL
40203,40204
2
Dword
Humidity
Humidity
Operating voltage Status input binary
HH HL LH
LL
40205,40206
2
Dword
Dew point
Dew point
Brightness
Status output
decimal
HH HL LH
LL