13.1.
Wrong assigned article number, delete article number
If you have accidentally assigned a wrong ESERA-Automation article number to a 1-Wire device, there are two
ways to fix it:
13.2.
Reset or change article number
You can reset the naming back to the original type or enter the correct article number.
To reset to the original type, enter the device designation without the "DS" abbreviation, e.g. for a DS18B20
temperature sensor the abbreviation "1820".
Command: SET,OWD,ART,OWD-Number,OWD-Type
, Example: SET,OWD,ART,2,1820
You can also enter another ESERA-Automation article number directly. Please note that there is no plausibility
check for the device when you enter it.
The correct input can be double-checked via the list output (e.g. LISTALL).
13.3.
Delete OWD
You can delete a 1-Wire sensor or a OWD number. With the next search run of the adaptive search, the device
should be available again at the previously deleted position in the OWD list.
Now you can enter the correct number.
Command: SET,OWD,DELNO,OWD number
, example: SET,OWD,DELNO,2
Note: The adaptive search must be activated (SET,OWB,SEARCH,1).
Selection of ESERA
sensors and actuators
Select OWD / 1-Wire Nummer
Delete OWD number
The highlighted OWD
number will be deleted.