Programming Manual Controller-Gateway-Station V1.0 R1.1
Page 62 of 77
A command can also be entered via the command field.
Command:
SET,OWD,NAME,OWD_number,name
Note: An individual text (name) with max. 18 characters can be added to an OWD device. The name is only
intended for a more accurate differentiation. No umlauts are accepted and all letters will be saved in upper case.
20.7.
Delete name of device (OWD)
Select the corresponding OWD number in the OWD device list and delete the existing name of the input field
"NAME". Then press the push button "SET" to accept the name.
An OWD name can also be deleted by command via the command field.
Command: SET,OWD,CNAME,OWD_number
Note: A deletion cannot be undone.
20.8.
Read name of device (OWD)
With the following command, the name of a 1-Wire device (OWD) can be output via the command field.
Command: GET,OWD,NAME,OWD_number
20.9.
Debug (DBG)
Different levels of debug output can be selected. Debug outputs start with the abbreviation
“DBG” for Debug
followed by various data. The formatting of the debug data is not fixed and is only intended as extended data
output during controller integration or debugging.
The debug outputs are switched off in the state of delivery.
20.10. Error registers
Various readable error registers are available. There are registers for each 1-Wire component (ERRORDEV and
sum-registers ERRORALL).
If a 1-Wire device is no longer readable, or data transmission is faulty, the ERRORDEV register of the
corresponding sensor as well as the sum-register (ERRORALL) are increased to a maximum of 5. If there are
more than 3 faulty queries in the component register (ERRORDEV), no more data is output for the corresponding
device.
The last valid data values are output up to the error limit. If the device, which was recognized as faulty, is re-
added to the 1-Wire network or if the data transmission is no longer faulty, the component register (ERRORDEV)
will be reset and the data output is continued.
Register ERRORDEV is reset after error-free reading of the 1-Wire device.