Programming Manual Controller-Gateway-Station V1.0 R1.1
Page 72 of 77
200
(list2)
List 1: Value: 0 = Disabled, 1 = Enabled
List 2: Value: 0 = Disabled or if enabled output
of the function extension
BTID
key
Password /
key for
Bluetooth
data
connection
factory
default key
is 1304
**
This function is only available for 1-Wire Controller 2 and 1-Wire Gateway 20.
22.5.2. One Wire Bus Command (OWB)
Queries affecting the entire 1-Wire network
GET
OWB COUNT
number
/value
Number of currently connected 1-Wire devices
COUNTMEM
value
Number of permanently stored 1-Wire devices
OWDID
value
Query, how is the identification of a 1-Wire device
output? With the serial number or the OWD
number?
0=OWD number
1=Serial number
OWDIDFORMAT
value
Query, how is the OWD serial number output?
0=
LIST0
list0
List output of all active 1-Wire devices with name,
serial number and function
Output Data header starts with 1-Wire Controller /
1-Wire Gateway number, "Data header LST0" and
time
LIST1
list1
List output of all 1-Wire devices with serial number
only
Output Data header starts with 1-Wire Controller /
1-Wire Gateway number, "Data header LST1" and
time
LIST2
list2
List output of all 1-Wire devices with serial number
and device type
Output data header starts with controller number,
"data header LST2" and time
LISTALL
list3
List output of all 1-Wire devices with name, serial
number, device type and status.
0-3=error counter, 5=not active
10=not occupied
Output Data header starts with 1-Wire Controller /
1-Wire Gateway number, "Data header LST" and
time
LISTALL1
list4
List output of all 1-Wire devices with name, serial
number, device type and status.
0-3=error counter, 5=not active
10=not occupied and OWD NAME
Output Data header starts with 1-Wire Controller /
1-Wire Gateway number, "Data header LST" and
time
LISTMEM
list4
List of OWD devices/modules permanently stored
in the 1-Wire Controller / 1-Wire Gateway
DEVICEID
1-30
value
Output of the 1-Wire Serial Number for a Module
SEARCH
value
Output of the search function,
Automatic search on/off
SEARCHTIME
value
Output of the cycle time for the component search
POLLTIME
value
Output 1-Wire Bus Polling cycle (polling time) in
seconds