© EPS Stromversorgung in 2022, this information is subject to change without notice
50
30000800_manual_psb_10000_4u_30kw_en_04
Group
Parameters & description
Analog interface REM-SB Action
Selects how the input pin REM-SB of the analog interface shall operate regarding the DC terminal con-
dition outside of analog remote control:
•
DC Off
= the pin can only switch the DC power stage off
•
DC On/Off
= the pin can switch the DC power stage off and on again, if it has been switched on before
from a different control location
Pin 6
Pin 6 of the analog interface (see section
“3.6.4.3. Analog interface specification”
) is by default as-
signed to signal both device alarms OT and PF. This parameter allows to also enable signaling only one
of both (3 possible combinations):
•
Alarm OT
= Pin 6 signals only alarm OT
•
Alarm PF
= Pin 6 signals only alarm PF
•
Alarm PF + OT
= Default, pin 6 signals either PF or OT
Pin 14
Pin 14 of the analog interface (see section
3.6.4.3) is by default assigned to only signal the device alarm
OVP. This parameter allows to also enable signaling the device alarms OCP and OPP in 7 possible
combinations:
•
Alarm OVP
= Pin 14 signals only OVP
•
Alarm OCP
= Pin 14 signals only OCP
•
Alarm OPP
= Pin 14 signals only OPP
•
Alarm OVP+OCP
= Pin 14 signals OVP or OCP
•
Alarm OVP+OPP
= Pin 14 signals OVP or OPP
•
Alarm OCP+OPP
= Pin 14 signals OCP or OPP
•
Alarm OVP+OCP+OPP
= Pin 14 signals any of the three alarms
Pin 15
Pin 15 of the analog interface (see section
3.6.4.3) is by default assigned to only signal the regulation
mode CV. This parameter allows to enable signaling the DC terminal status (2 options):
•
Regulation mode
= Pin 15 signals the CV regulation mode
•
DC status
= Pin 15 signals the DC terminal status
VMON/CMON
Configures how the actual values of voltage and current are represented. If not listed otherwise, the
setting doesn’t affect the selected signal range (0-5 V or 0-10 V).
•
Default
= Current (sink or source mode) on pin 10 (CMON), voltage on pin 9 (VMON)
•
Actual current (EL)
= Pin 10 only signals the actual current in sink mode (EL)
•
Actual current (PS)
= Pin 10 only signals the actual current in source mode (PS)
•
Mode A
= Current of source mode (PS) on pin 9, current of sink mode (EL) on pin 10, the voltage is
not signaled in this mode
•
Mode B
= Current of sink mode (EL) on pin 9, current of source mode (PS) on pin 10, the voltage is
not signaled in this mode
•
Actual current (EL) + (PS)
= Pin 10 signals a combination of the current in sink and source mode as
-100%...0...100% whereas 0% is put in the center of the analog signal range, it means either at 5 V or
2.5 V. Each of both actual values only has half resolution.