© EPS Stromversorgung in 2022, this information is subject to change without notice
12
30000800_manual_psb_10000_4u_30kw_en_04
1.8.3
Specific technical data
General specifi cations
AC input
Voltage, Phases
Range 1: 208 V, ±10%, 3ph AC (with DC output power derating to 18 kW)
Range 2: 380 - 480 V, ±10%, 3ph AC
Frequency
45 - 65 Hz
Power factor
ca.
0.99
Leakage current
<10 mA
Inrush current / Phase current
≤
56 A
Overvoltage category
2
DC output static
Load regulation CV
≤0.05% FS
(0 - 100% load, constant output voltage and constant temperature)
Line regulation CV
≤0.01% FS
(208 V - 480 V AC +10% supply voltage, constant load and constant temperature)
Stability CV
≤0.02% FS
(during 8 h of operation, after 30 minutes warm-up, at constant output voltage, load and temperature)
Temperature coeffi cient
CV
≤30ppm/°C
(after 30 minutes of warm-up)
Compensation (remote sense)
≤5% U
Nominal
Load regulation CC
≤0.1% FS
(0 - 100% load, constant output voltage and constant temperature)
Line regulation CC
≤0.01% FS
(208 V - 480 V AC +10% supply voltage, constant load and constant temperature)
Stability CC
≤0.02% FS
(during 8 h of operation, after 30 minutes warm-up, at constant output voltage, load and temperature)
Temperature coeffi cient
CC
≤50ppm/°C
(after 30 minutes of warm-up)
Load regulation CP
≤0.3% FS
(0 - 100% load, constant output voltage and constant temperature)
Load regulation CR
≤0.3% FS + 0.1% FS current
(0 - 100% load, constant output voltage and constant temperature)
Protective functions
OVP
Overvoltage protection,
adjustable 0 - 110% U
Nominal
OCP
Overcurrent protection,
adjustable 0 - 110%
I
Nominal
OPP
Overpower protection,
adjustable 0 - 110%
P
Nominal
OT
Overtemperature protection
(DC output shuts down in case of insuffi cient cooling)
DC output dynamic
Rise time 10 - 90% CV
≤10 ms
Fall time 90 - 10% CV
≤10 ms
Rise time 10 - 90% CC
≤2 ms
Fall time 90 - 10% CC
≤2 ms
Display accuracy
Voltage
≤0.05% FS
Current
≤0.1% FS
Insulation
AC input to DC output
3750 Vrms
(1 minute, creepage distance >8 mm) *1
AC input to case (PE)
2500 Vrms
DC output to case (PE)
Depending on the model, see model tables
DC uutput to interfaces
1000 V DC (models up to 360 V rating), 1500 V DC (models from 500 V rating)
Interfaces digital
Built-in, galvanically isolated
USB, Ethernet (100 MBit) for communication, 1x USB host
for data acquisition
Optional, galvanically isolated
CAN, CANopen, RS232, ModBus TCP, Profi net, Profi bus, EtherCAT, Ethernet
Interfaces analog
Built-in, galvanically isolated
15 pole D-Sub
Signal
range
0 - 10 V or 0 - 5 V (
switchable
)
Inputs
U, I, P, R,
remote control on/off, DC output on/off, resistance mode on/off
Outputs
Monitor U and I, alarms, reference voltage, DC output status, CV/CC regulation mode
Accuracy
U / I / P / R
0 - 10 V: ≤0.2%, 0 - 5 V: ≤0.4%
*1 Models up to 80 V DC rating have reinforced insulation while all other models from 200 V DC rating have basic insulation