30000800_manual_psb_10000_4u_30kw_en_04
IF Settings
Description
CA
N
Baud rate
Setup of the CAN bus speed or baud rate in typical value between 10 kbps and
1Mbps. Default:
500 kbps
ID Format
Selection of the CAN ID format and range between
Standard
(11 Bit ID, 0h...7ffh)
and
Extended
(29 Bit, 0h...1fffffffh)
Termination
Activates or deactivates CAN bus termination with a built-in resistor. Default: off
Data length
Determines the DLC (data length) of all messages sent from the device.
Auto
= length can vary between 3 and 8 bytes
Always 8 Bytes
= length is always 8, filled up with zeros
Base ID
Setup of the CAN base ID (11 Bit or 29 Bit, hex format). Default:
0h
Broadcast ID
Setup of the CAN broadcast ID (11 Bit or 29 Bit, hex format). Default:
7ffh
Base ID Cyclic Read
Setup of the CAN base ID (11 Bit or 29 Bit, hex format) for cyclic read of several
object groups. The device will automatically send object data to the IDs defined
with this setting. For more information refer to the programming guide. Default:
100h
Base ID Cyclic Send
Setup of the CAN base ID (11 Bit or 29 Bit, hex format) for cyclic send of set values
along with status. For more information refer to the programming guide. Default:
200h
Cyclic Read Time: Status
Activation/deactivation and time setting for the cyclic read of status from the
adjusted
Base ID Cyclic Read
Range: 20...5000 ms. Default:
0 ms
(deactivated)
Cyclic Read Time: Set values (PS)
Activation/deactivation and time setting for the cyclic read of set values of U & I
(source mode) from the adjusted
Base ID Cyclic Read + 2
. Range: 20...5000 ms.
Default:
0 ms
(deactivated)
Cyclic Read Time: Limits values 1 (PS)
Activation/deactivation and time setting for the cyclic read of adjustment limits of
U & I (source mode) from the adjusted
Base ID Cyclic Read + 3
.
Range: 20...5000 ms. Default:
0 ms
(deactivated)
Cyclic Read Time: Limits values 2 (PS)
Activation/deactivation and time setting for the cyclic read of adjustment limits
of P & R (source mode) to the adjusted
Base ID Cyclic Read + 4
. Range: 20...5000
ms. Default:
0 ms
(deactivated)
Cyclic Read Time: Actual
Activation/deactivation and time setting for the cyclic read of actual values from
the adjusted
Base ID Cyclic Read + 1
Range: 20...5000 ms. Default:
0 ms
(deactivated)
Cyclic Read Time: Set values (EL)
Activation/deactivation and time setting for the cyclic read of set values of I, P
and R (sink mode) from the adjusted
Base ID Cyclic Read + 5
. Range: 20...5000
ms. Default:
0 ms
(deactivated)
Cyclic Read Time: Limit values (EL)
Activation/deactivation and time setting for the cyclic read of adjustment limits
of I, P and R (sink mode) from the adjusted
Base ID Cyclic Read + 6
. Range:
20...5000 ms. Default:
0 ms
(deactivated)
Module firmware
CAN module firmware version
IF Settings
Description
RS
23
2 Baud rate
The baud rate is selectable, other serial settings can’t be changed and are defined
like this: 8 data bits, 1 stop bit, parity = none
Baud rates:
2400Bd
,
4800Bd
,
9600Bd
,
19200Bd
,
38400Bd
,
57600Bd
,
115200Bd