2.3.8
Connection of remote sensing
•
Remote sensing is only effective during constant voltage operation (CV) and for other regulation modes
the sense input should be disconnected, if possible, because connecting it generally increases the os-
cillation tendency
•
The cross section of the sense cables is noncritical. Recommendation for cables up to 5 m (16.4 ft):
use at least 0.5 mm²
•
Sense cables shouldn’t be twisted, but laid close to the DC cables, i. e. Sense- cable close to DC- cable
to the load etc. to damp or avoid possible oscillation. If necessary, an additional capacitor should be
installed at the load/consumer to eliminate oscillation
•
The Sense+ cable must be connected to DC+ on the load and Sense- to DC- at the load, otherwise the
sense input of the power supply can be damaged. For an example see Figure 14 below.
•
In master-slave operation, the remote sensing should be connected to the master unit only
•
The dielectric strength of the sense wires must always at least match the DC voltage rating!
Dangerous voltage on the sense connectors! The sense cover must always be installed.
Figure 14 - Example for remote sensing wiring (DC terminal and Sense terminal covers left way for illustrative purposes)
Allowed connection schemes: