1 PASSWORD ????
0 * * * (6 3 4 3)
2 BASIC SETTINGS
[ NO ]
14 POWER 1st STAGE
[ 0...255] kvar
15 CHANGE PASSWORD
[ NO ]
16 - 19 PASSWORD
[ 6 ] 3 4 3
20 ERROR-BACKLIGHT
[ PINK ]
3 SWITCH. OPERATION
RESET [ NO ]
4 OPERATING TIME
RESET [ NO ]
5 INTEGRATION TIME
[ 1 ] sec.
6 SWITCH. POWER
max [ 160 ] kvar
10 SWITCH.OPER.WARN
[ 50 000 ]
9 OPERATING LOCK
[ NO ]
8 SWITCH. TRIGGER
CAP [ 66 ] %
7 SWITCH. TRIGGER
IND [ 66 ] %
12 DISPLAY
[ cosPhi -0.10 ... +0.10 ]
11 CONTROL
[ MEAN VALUE ]
13 V - CONNECTION
[ N - L1 - L2 - L3 ]
BACK TO 1
=====
EXPERT-MODE 1
=====
=====
EXPERT-MODE 2
=====
- 41 -
1 PASSWORD ????
0 * * * (6 3 4 3)
5 OVERVOLTAGE
LIMITING VALUE
460 V [ 115 ] %
6 OVERCOMPENSATED
[ Q-DIFF ]
7 UNDERCOMPENSATED
[ Q-DIFF ]
8 SWITCH.OPERATION
C1 RESET [ NO ] until
C15 RESET [ NO ]
9 OPERATION TIME
C1 RESET [ NO ] until
C15 RESET [ NO ]
2 DISPLAY / ALARM
[ YES ]
Release [YES] or
blocking [NO] of
following reports
or alarms:
MEAS. VOLTAGE
OVERVOLTAGE
OVERCOMPENSATED
UNDERCOMPENSATED
HARMONICS !
OVERTEMPERATURE
OVERCURRENT
UNDERVOLTAGE
SWITCH.OPERATION
MEAS.CURRENT < ??
ERROR COM 1
ERROR COM 2
MODBUS-ERROR
SWITCH.OFF
STOP
SWITCH. ON
SYSTEM CURRENT <?
BUS-ERROR-EXTERN
C-DEFECT
SYSTEM CURRENT > 0
SYSTEM OVERLOAD
EXTERNAL ERROR
RELAY ERROR
RESERVE
3 ALARMRELAY
DELAY
[ 10 ] min
4 UNDERVOLTAGE
LIMITING VALUE
200 V [ 50 ]%
BACK TO