- 22 -
Section 10: SERVICE MENU / Fault memory
This service menu can be reached by the operating-mode key.
The stored maximum values of the grid parameters can be displayed here as well as the
number of switching operations of the individual capacitor steps and their operation time.
The desired stage (in square brackets) is selected via the arrow keys.
In addition, a fault memory is available where the last fault events of the system are
stored in plain text (e.g. short-term over temperature or over voltage).
Action
Display
Unit
3-phase
ENTER
1 max VOLTAGE
in V
L1 ... L3
ENTER
2 max. CURRENT
in A
L1 ... L3
ENTER
3 max. REACTIVE POWER
in kvar
L1 ... L3
ENTER
4 max. ACTIVE POWER
in kW
L1 ... L3
ENTER
5 max. APPARENT POWER
in kVA
L1 ... L3
ENTER
6 max. TEMPERATURE
in °C /°F
ENTER
7 max. THD - V / THD-I
in % /
L1 ... L3
bargraph
ENTER
8 MAX. VALUE RESET
ENTER
9 ENERGY RESET
ENTER 10 Switch.OPERATIONS C [1] -
é
/
ê
to
C [15]
ENTER 11 OPERATING TIME C [1]-
in h
é
/
ê
to C [15]
in h
ENTER 12 ERROR MEMORY
in plaintext
with time-stamp
ENTER 13 ERROR MEMORY RESET
ENTER
Back to 1
The Time-stamp can be selected via arrow-keys.
Example ERROR display:
overcompensated in phase L3
with date / time stamp
12 ERROR MEMORY
SERVICE
capacitive Load
too high
overcompensated L3
01.03.16 - 15:58:00