=== PROGRAM-MODE ===
CONTROL-MODE [4]: 3-phase measuring / max. 15 three-phase capacitors
Connection of measuring current and measuring voltage refer to page 6.
Values displayed and calculated per phase. Controlling done with max. 15 outputs according
to maximum or mean-value of the reactive power
CONTROL-MODE [5]: 1-phase measuring / max. 15 three-phase capacitors
Only current transformer in L1 required
Connection of measuring current and measuring voltage see page 6
Values extrapolated to all phases (balance assumed)
Measuring complies with conventional measuring for switching of three-phase capacitors.
CONTROL-MODE [6]: 1-phase measuring / max. 15 three-phase capacitors
with internal capacitor current measurement
According variant 5, but the free current inputs (L2 or L3) are used for
internal
capacitor
current
measurement for real monitoring of capacitors.
Connection of measuring current and measuring voltage see page 6 - pict. 3!
CONTROL-MODE [7]: 3-phase measuring / max. 15 three-phase capacitors
External m
easurement for real monitoring of capacitors via 1...6 pcs. devices „MMI6000”
Programming of numbers of MMI in C-TEST MODE
Can be used for 1...6 cabinet-parts
Connection of MMI6000 via LAN-cables (COM2 at BR7000)
Connection of BR7000: compare Control-Mode 4
CONTROL-MODE [8]: 1-phase measuring / max. 15 three-phase capacitors
External m
easurement for real monitoring of capacitors via 1...6 pcs. devices „MMI6000”
Programming of numbers of MMI in C-TEST MODE
Can be used for 1...6 cabinet-parts
Connection of MMI6000 via LAN-cables (COM2 at BR7000)
Connection of BR7000: compare Control-Mode 5
CONTROL-MODE [9]: 3-phase measuring / max. 3x5 single phase capacitors L-N
correspond to Control-Mode 1, but remote measurement via „MMI7000"
Can be used if CT is far away from the controller or MMI7000 already exists in the system
Connection of MMI7000 is done via LAN-cable to COM2 at BR7000
Connection of MMI7000: compare connection of BR7000 at page 6 / pict.1
Connection of BR7000: 3-phase voltage only, no connection of CTs needed.
CONTROL-MODE [10]: 3-phase measuring / max. 15 three-phase capacitors
correspond to Control-Mode 4, but remote measurement via „MMI7000"
Connection of MMI7000 is done via LAN-cable to COM2 at BR7000
Connection of MMI7000: compare connection of BR7000 at page 6 / pict.1
Connection of BR7000: 3-phase voltage only, no connection of CTs needed.
CONTROL-MODE [11]: 3-phase measuring / max. 15 three-phase capacitors
Remote measurement and internal real monitoring of capacitors (L1...L3)
correspond to Control-Mode 6, but remote measurement via „MMI7000"
internal real monitoring of capacitors via current inputs L1...L3
e.g. Monitoring for 1...3 cabinets
Connection of MMI7000 is done via LAN-cable to COM2 at BR7000
Connection of MMI7000: compare connection of BR7000 at page 6 / pict.1
CONTROL-MODE [12]: 3-phase measuring / max. 15 three-phase capacitors
Remote measurement and internal real monitoring of capacitors (L1...L3)
correspond to Control-Mode 6, but remote measurement via „MMI7000"
internal real monitoring of capacitors via current inputs L1...L3
--> Single-phase monitoring for 1 cabinet
Connection of MMI7000 is done via LAN-cable to COM2 at BR7000
Connection of MMI7000: compare connection of BR7000 at page 6 / pict.1
- 13 -