=== PROGRAM-MODE ===
39 HARMONICS
[ --,-- ]%
(--.-- ... 25.5)%
Threshold value THD-I (in%). In case this value is exceeded a message will be
displayed.
40 CLOCK [ HH:MM ], DATE
[DD.MM.YY]
Set system-time and date
(Due to an internal battery the time will be kept even in case of power loss)
Selection with
é
/
ê
. Save/continue with ENTER
41 Q-OFFSET (L1-L3)
[ NO ]
( multiple of 1st stage)
H
42 CONTRAST
[ 4 ]
( 0...10)
Adjustment of display contrast for best readability
40 BASIC SETTINGS
[ NO ] (YES/NO)
When selecting YES and confirmated with ENTER, all parameters are set back to
the basic settings of the panel builder (optimum values for the system if
the controller has been delivered together with the PFC-system).
If the controller has been delivered ex works, this point corresponds to the
default settings.
ATTENTION: All user settings get lost !
Section 6.1: PROGRAMMING LOCK
As a protection against unauthorized changes of the system parameters, the device is
equipped with a programming lock. This can be activated in the EXPERT MODE. When the
lock is active, all parameters can be checked but not changed.
Alternatives:
Lock active / Not active / Automatic activation after 24 h
ere an additional capacitive power is switched on independent from target
cos-phi and controlling - e.g. transformer direct compensation.
(value programmable via arrow-keys).
- 18 -