- 35 -
Annex 3: Technical Data
Type series
Operating voltage
Measuring voltage (3-phase)
Measuring current (3-phase)
Power consumption
Sensitivity
Switching power
Relay outputs for capacitor branches
Alarm relay
Message relay
Relay for panel fan
Switching power of relay outputs
Number of active outputs
Operation and display
Menu Languages
Number of control series
User-defined control series
Controlling
Modes of operation
(1- and 3-phase)
Control principle
Automatic initialization
Meas. of individual capacitor step current
Target- cos
ϕ
nd
2 target cos
ϕ
(time- or result controlled)
Switch on time
Switch off time
Discharge time
Internal clock / several timers
Manual operation
Fixed steps / skip steps
Zero voltage release
BR 7000....
110...440 V~, +/-10%, 50 / 60Hz
3 · 30...440 V~ (L-N) / 50...760V~ (L-L)
3 · X : 5 / 1A selectable
< 5 W
50 mA / 10mA
15 relays: freely programmable for switching of
single- and three-phase capacitors
1
1, programmable
1
250VAC, 1000W
programmable
illuminated full graphic display 128x64 dot
Ger / E / ES / RU / TR
20
1 via editor
true controlling of each phase ( L-N ) und ( L-L )
1- phase: up to 3 · 5 single phase capacitors
3- phase: up to 15 three-phase capacitors
mixed Mode: for balancing and compensation
series switching, circular switching,
self-optimized intelligent switching,
4-quadrant operation
possible
possible
0.1 ind. ... 0.1 cap adjustable
0.1 ind. ... 0.1 cap adjustable
selectable from 1 sec. to 130 min
selectable from 1 sec. to 130 min
selectable from 1 sec. to 130 min
yes
yes
programmable
standard