=== PROGRAM-MODE ===
23 EXTERNAL INPUT
[ NO ]
( 1...8 )
Setting of the desired action upon applying a control voltage of 110...230V~ at
the external input.
1 - NO
(no action)
2- 2nd parameter set (switch over to 2nd parameter set).
This selection simultaneously activates the following points 24…37
for programming of the values of the 2nd parameter set.
3 - External error (Display of an error message)
4 - Remote - Switch ON
5 - Remote - Switch OFF
6 - Remote - Stopp
7 - Coupling operation parallel
COM2
(Input for signal of coupling switch)
8 - Coupling operation Master/Slave COM2
(Input for signal of coupling switch)
Description of coupling operation s.page 31
Programming of 2nd parameter set
(only active if 23 EXTERNAL INPUT is set to 2nd parameter set)
As a standard, the values of the 2nd parameter set equal the values of the normal
parameter set. Possible applications are for example: changing of target cos-phi, switch-
over of current transformer or switch-over the switching times.
By triggering a 110...230V~ signal at the external input, the 2nd parameter set is
activated with following values:
The programming of the 2nd parameter set is performed equivalent to the
programming of the 1st set parameters (3-19)
38 HARMONICS [ 7 ]%
(--.-- ... 25.5)%
Threshold value THD-V (in%). In case this value is exceeded a message will be displayed.
THD-V ist the ratio of the geometric sum of unequal harmonics to the 1st harmonic. In any
case, a warning will be displayed. Warning via message relay will only be executed if
selected in 22.
24. I-converter prim
25. I-converter sec
26. End stop
27. Control serie
28. Control principle
29. Power 1st stage
30. Target cos-Phi
nominal value
31. 2nd target cos-Phi NO/supply/Timer
32. 2nd target cos-Phi nominal value
33. Switch on time target cos-Phi-2
34. Switch off time target cos-Phi-2
35. Connecting time
36. Disconnecting time
37. Discharge time