TUTORIALS
Using Valves to Control a Multi-Head Machine
201 |
P a g e
Copyright © 2021 BF ENTRON and/or its affiliates. All rights reserved
Product Model:
iPAK2v2
Firmware Version:
V2.10
May 22 | Doc No 700253-2
5
Look at the Error/Message
window. If you see
“
RESTART REQUIRED
”, then
the control must be restarted.
6
Close the “
Edit Control
Parameters
” window
by
clicking the
symbol.
7
Press the
Restart
Button to
cycle power to the control
Table 76: Configure iPAK2v2 for Multi-Electrodes
10.2.3
Program the WAV Output for Each Weld Program in the Cascade Sequence
The
WAVx
output will be selected with each weld program to define which Weld Air Valve will close during the
execution of the weld program.
provides an example of setting the
WAVx
output on four different weld
programs in
NetFlash™
. All four programs are assigned to
Electrode 0
which means the weld current will be output
through the same weld transformer.
Figure 77: Example of WAV Settings on Weld Program for Multi-Head Machine
The step-by-step instructions program the sequence shown in
NetFlash™