Force Calibration
The iPAK2v2 weld controller has the ability to control weld force and read the weld force via analog signals. The analog
input allows the control to read the output of an external force sensor (load cell) or a proportional pressure sensor to
measure force. The analog output can be used to control a proportional air regulator valve to control weld force.
The analog input and output signals operate between 0
–
10V. The linear relationship between mV signal and the force
must be programmed into the iPAK2v2 during installation.
The calibration is based on a two-point lookup table and requires a weld force gauge.
The weld force can be calibrated in terms of kN or lbf. The units of measure are defined in the configuration section.
Refer to the Configure the Control section for more information.
The Force calibration parameters are defined in
Parameter
Units
Range
Description
OUT Point 1
mV
0 - 10000
Analog output (point 1)
OUT Point 1
kN/lbf
Measured output force (point 1)
OUT Point 2
mV
0 - 10000
Analog output (point 2)
OUT Point 2
kN/lbf
Measured output force (point 2)
IN Point 1
mV
0 - 10000
Analog input (point 1)
IN Point 1
kN/lbf
Measured input force (point 1)
IN Point 2
mV
0 - 10000
Analog input (point 2)
IN Point 2
kN/lbf
Measured input force (point 2)
Table 8: Force Calibration Parameters
The default values for the kN and lbf units are shown in Figure 16 and Figure 17 respectively.
Figure 16: Default Force Calibration Table Values in Units of kN