Emergency Unit Monitoring (00÷02)
The emergency unit will be tested by shutting of the power
to the control panel and open the door with the emergency
unit. The test is never done in operation mode selection
OPEN and normally not in OFF, unless parameter 37
“Emergency Action In OFF Mode” is set to On, see below.
Authorities can demand that the emergency unit is moni-
tored on a regular
basis, see parameter 40 “Emergency Unit Test Interval” be-
low. Half an hour before this time has elapsed the following
outer impulse generates an emergency opening test . If there
is no outer impulse within the next half hour, the operator
control unit generates the opening impulse by it self (ghost
impulse). The test is also always performed after a Reset
and after changing operation mode selection from a position
where a test is not done to a position where the test is made.
00
= Off.
01
= Convenience monitoring. Is a simpler one-channel
monitoring. Convenience monitoring can be used for
monitoring battery.
02
= Redundant monitoring. Is a redundant two-channel
monitoring that is a demand for escape route according
to: EN16005 or DIN18650.
*NOTE
: on DAS200RF set to 02.
*NOTE
: on DAS00RG is not visible and it is set up on 02.
Partial Open Position (00-99%)
Sets the “winter opening” size.
NOTE
: A building is certified for a certain COW. Depending
on how many people that is allowed to be in the specific
area there also has to be a certain opening width. Partial
open position must be set to 80% of the certified distance
in escape routes.
(DAS200)
(DAS200HD/RF)
(DAS200RG)
Opening direction (00÷01)
00
= 1 wing Right.
01
= 1 wing Left or 2 wings.
NOTE
: On DAS200RG this parameter cannot be selected,
the opening direction is defined with the position of the
belt attachment bracket.
Hold force (00÷60 N)
Adjustment of the force used to keep the door in closed position.
Run Program (01÷05)
Performance adjustment. Sets how fast or slow the door
shall accelerate or break.
01
= Smooth, for light doors.
05
= Max Performance. For heavy doors.
Inner Impulse (motion) Monitoring (00÷01)
According to EN 16005 or DIN18650 it is a demand to have
Inner impulse monitoring = On in escape routes.
00
= Disables monitoring.
01
= Enables monitoring.
*NOTE
: on DAS200RF set to 01.
*NOTE
: on DAS200RG this parameter is set to 01.
AUTOMATIC*