Function Select terminal 2 - DAS902MP (00÷03)
00
= No function.
01
= Close function. This impulse will immediately close the
door, even during opening, and remain closed as long
as the Close impulse is active. The electro-mechanical
lock will lock the closed door.
May not be used on an escape route door.
02
= DO NOT USE.
03
= Inner impulse 2. When two inner impulses are to be
used. Sets input to inner impulse 2.
Fire Impulse Function, terminal 18-19 - DAS902MP (00÷01)
Depending on configuration in Emergency Action (36),
the door will open or close on fire impulse. Fire impulse
override presence impulse. At closing, the door will not
reopen on jam.
00
= Off.
01
= On.
Emergency Open Impulse Function, terminal 5 - DAS902MP
(00÷01)
Fireman’s opening.
00
= Off.
01
= On.
Emergency Open Impulse Configuration, terminal 5 - DA-
S902MP (00÷01)
Configures the button used for Fireman’s opening.
00
= N.O.
01
= N.C.
Operation Mode Selector Functio, terminal 9÷14 - DA-
S902MP (00÷01)
Switch / timer / relay
00
= Off.
01
= On (Not allowed in escape route, according to EN16005
and DIN18650).
Lock Configuration, terminal 16-17 - DAS902MP (10÷11)
Bi-stable lock used as night lock of escape routes.
10
= No Lock.
11
= Bi-stable lock.
Function Select, terminal 6 - DAS902MP (00÷02)
00
= No function.
01
= Sustainable Disable Disables Sustainable drive mode.
It is possible to disable sustainable drive mode. As long
as contact is active the operator will run with full power .
02
= Enable the Mode Selector with a key (only COM500ER)
DAS909MP mode selector and all other Mode Selectors
are not affected by this parameter.
When parameter is set to value 02 the OMS is locked.
If an impulse is given on IOU TB:6 the indication LED on
OMS will be steady red during 15 seconds and it is pos-
sible to change mode selection (set parameter B1= 00).
Priority of the operation mode selector DAS902MP, temi-
nals 9÷14 (25÷99)
FUTURE USE