14. Routine maintenance plan
Perform the following operations and checks every 6 months, according to the intensity of use of
the automation.
With power supply and batteries disconnected:
-
Clean and lubricate the mobile parts (the carriage slide guides and the floor guides).
-
Check the belt and its tension.
-
Clean sensors.
-
Check the stability of the automatic system and make sure that all screws are correctly
tightened.
-
Check the alignment of the door wings, the position of the end stops, and the correct intro-
duction of the blocking device.
With power supply and batteries connected:
-
Check the blocking system is working correctly.
-
Check the stability of the automation, and make sure it moves smoothly.
-
Check that all control functions are operating correctly.
-
Make sure the command and safety sensors are working correctly.
-
Make sure the forces developed by the automation meet the requisites of the applicable
regulations.
-
Check the correct functioning of the batteries.
NB: for spare parts, see the spares price list.
i
i
Only use original spare parts for repairing or replacing products.
The installer must supply all information concerning the automatic, manual and emer-
gency operation of the motorised automation or gate, and must provide the user with the
operating instructions.
The installer must prepare and keep a maintenance record showing all the routine and
extraordinary maintenance work carried out.