RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
83
EN
HANCED
TEC
HNOLOGY
6.1.2. Setting
PRIMARY SETTING / SYSTEM SETUP / CURRENT SENSING / PHA CT Ratio
Range
1 ~ 1200
Default
1000
Step
1
Enter the phase CT primary current value.
PRIMARY SETTING / SYSTEM SETUP / CURRENT SENSING / GND CT Ratio
Range
1 ~ 1200
Default
1000
Step
1
Enter the ground CT primary current value.
PRIMARY SETTING / SYSTEM SETUP / CURRENT SENSING / SEF CT Ratio
Range
1 ~ 1200
Default
1000
Step
1
Enter the sensitive earth CT primary current value.
[CURRENT SENSING]
PHA CT Ratio: 1000
GND CT Ratio: 1000
>SEF CT Ratio: 1000
[CURRENT SENSING]
PHA CT Ratio: 1000
>GND CT Ratio: 1000
SEF CT Ratio: 1000
[CURRENT SENSING]
>PHA CT Ratio: 1000
GND CT Ratio: 1000
SEF CT Ratio: 1000