RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
20
EN
HANCED
TEC
HNOLOGY
DIAGNOSTIC EVENT RECORDER
y
Trigger Source
System Power(AC, Battery,
±
12V, +5V)
A/D Conversion(A/D Fail, Reference Voltage1, Reference Voltage 2)
Sleep Mode
Power Down Mode(Charge Volt High Alarm)
Setting Change
Gas Status
Alarm Status, etc.
NOTE :
According to a recloser type, there may be no diagnosis of gas pressure status.
y
Trigger Time : each 1/4 cycle
y
Trigger type : Pick up and Dropout
y
Storage Capacity : Last 512 Events
LOAD PROFILE
y
Trigger Source
Demand Current(A, B, C, G)
Demand Real Power(A, B, C, 3
ф
)
Demand Reactive Power(A, B, C, 3
ф
)
Demand Power Factor(3
ф
)
Demand Energy( 3
ф
)
Trigger Time : 5, 10, 15, 20, 30, 60minute
y
Storage Capacity : Total 5120 Events, 213days/60min.
FAULT TRIP EVENT RECORDER - Option
y
Trigger Source
Trigger elements : A,B,C,G, SEF phase and Negative Sequence
Current[A] each phase when fault occurs
y
Trigger Time : each 1/4 cycle
y
Trigger type : fault occurrence
y
Storage Capacity : Last 512 Events