PRIMARY SETTING / PROTECTION / INTERVALS / Reclose 1
Range
0.50 ~ 600.00 sec(prior to Ver 6.11 of EVRC2A)
0.10 ~ 600.00 sec(from Ver 6.11 of EVRC2A)
Default
0.60
Step
0.01 sec
This setting is used to change the first reclose interval time between the
first trip operation and the close operation.
PRIMARY SETTING / PROTECTION / INTERVALS / Reclose 2
Range
1.00 ~ 600.00 sec
Default
2.00
Step
0.01 sec
This setting is used to change the first reclose interval time between the
first trip operation and the close operation.
PRIMARY SETTING / PROTECTION / INTERVALS / Reclose 3
Range
1.00 ~ 600.00sec
Default
15.00
Step
0.01
This setting is used to change the first reclose interval time between the
first trip operation and the close operation.
PRIMARY SETTING / PROTECTION / INTERVALS / Reclose 4
Range
1.00 ~ 600.00 sec
Default
15.00
Step
0.01 sec
This setting is used to change the first reclose interval time between the
first trip operation and the close operation.
PRIMARY SETTING / PROTECTION / INTERVALS / Reset T(AR)
Range
1.00 ~ 600.00 sec
Default
30.00
Step
0.01 sec
Select Reset time for auto reclose.
The Reset time for auto reclose is used for the recloser to automatically
reclose.
Traditionally, the Reset time for auto reclose setting is used to set time
for a delay longer than the incomplete sequence.
If any overcurrent elements are picked up, the reset timer is reloaded.
Reset timer can only count if all the overcurrent elements are cleared.
[INTERVALS]
Reclose 3: 15.00
Reclose 4: 15.00
>Reset T(AR): 30.00
[INTERVALS]
Reclose 2: 2.00
Reclose 3: 15.00
>Reclose 4: 15.00
[INTERVALS]
Reclose 1: 0.60
Reclose 2: 2.00
>Reclose 3: 15.00
[INTERVALS]
Reclose 1: 0.60
>Reclose 2: 2.00
Reclose 3: 15.00
[INTERVALS]
>Reclose 1: 0.60
Reclose 2: 2.00
Reclose 3: 15.00