![Entec EVRC2A-N6-NT Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/entec/evrc2a-n6-nt/evrc2a-n6-nt_user-manual_2414428069.webp)
RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
59
EN
HANCED
TEC
HNOLOGY
COMMUNICATION/ PORT SETUP/ PORT2-RS232
/
Line Type
Range
DIALUP, 2-WIRE, 4-WIRE
Default
4-WIRE
Step
~
Select a modem for communication.
DIALUP :
Dial-Up modem1 is used.
2-WIRE :
2-wire private line is used and continuously Carrier is
monitored to control data flow by DCD(Data Carrier Detect).
4-WIRE :
4-wire private line is used and RTS(Request To Send) and
CTS(clear to Send) signal are used to control data flow.
COMMUNICATION/ PORT SETUP/ PORT2-RS232
/
CTS Function
Range
OFF, ON
Default
ON
Step
~
Select whether to use CTS signal or not.
OFF :
Regardless of CTS signal, transfer a data.
ON :
After confirming CTS signal is Asserted, transfer a data.
COMMUNICATION/ PORT SETUP/ PORT2-RS232
/
DCD Function
Range
OFF, ON
Default
OFF
Step
~
Set whether to use DCD signal or not.
OFF :
Regardless of DCD signal, transfer a data.
ON :
After confirming DCD signal is Asserted, transfer a data.
COMMUNICATION/ PORT SETUP/ PORT2-RS232
/
RTS Function
Range
OFF, ON, AUTO
Default
AUTO
Step
~
Set whether to use RTS signal and the mode or not.
OFF :
RTS signal of EVRC2A is always OFF(Deassert).
ON :
RTS signal of EVRC2A is always ON(Assert).
AUTO :
On requesting data transfer to Modem, after RTS signal of
EVRC2A is on and after data transfer completion, RTS signal of
EVRC2A is off.
[PORT1-RS232]
>
CTS Function: ON
>
DCD Function: OFF
>RTS Function: AUTO
[PORT1-RS232]
>
CTS Function: ON
>DCD Function: OFF
>
RTS Function: AUTO
[PORT1-RS232]
>
Line Speed: 19200
>
Line Type: 4-WIRE
>CTS Function: ON
[PORT1-RS232]
>
Stop Bit: 1
>Line Type: 4-WIRE
>
CTS Function: ON