RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
17
EN
HANCED
TEC
HNOLOGY
Fault Locator
Total Length of Feeder .............................................. 0.1 to 99.9 of 0.1km
Real impedance of the feeder positive seq. ............... 0.1 to 6000.0 of 0.1ohms
Imaginary impedance of the feeder positive seq. ...... 0.1 to 6000.0 of 0.1ohms
Real impedance of the feeder zero seq. ..................... 0.1 to 6000.0 of 0.1ohms
Imaginary impedance of the feeder zero seq ............. 0.1 to 6000.0 of 0.1ohms
Power Quality - Option
Detect Function of Supply Outage. ........................... DISABLE, ENABLE
Supply Outage Duration ............................................ 1 to 3600 in steps of 1s
Detect Function of Voltage Sag. ................................ DISABLE, ENABLE
Detect Level of Voltage Sag. ..................................... 0.30 to 0.95 in steps of 0.01 x VT
Detect Time of Voltage Sag. ...................................... 1 to 60 in steps of 1cycle
Detect Function of Voltage Swell. ............................. DISABLE, ENABLE
Detect Level of Voltage Swell. .................................. 1.05 to 1.25 in steps of 0.01 x VT
Detect Time of Voltage Swell. ................................... 1 to 60 in steps of 1cycle
Detect Function of Voltage Unbalance. ..................... DISABLE, ENABLE
Detect Level of Voltage Unbalance ........................... 1 to 100 in steps of 1%
Detect Time of Voltage Unbalance ............................ 0.1 to 60.0 in steps of 0.1s
Detect Function of Current Unbalance. ..................... DISABLE, ENABLE
Detect Level of Current Unbalance ........................... 1 to 100 in steps of 1%
Detect Time of Current Unbalance ............................ 0.1 to 60.0 in steps of 0.1s
Limit Current to Detect Current Unbalance .............. 1 to 630 in steps of 1A
Level Accuracy .......................................................... ± 5%
NOTE :
The setting for voltage/current unbalance is supported from version 6.12 of
EVRC2A-N6,NT.
Gas Low Lock - Option
Pickup Low Level ..................................................... 0.1bar
External Trip & Lock - Option
Use Input Port ........................................................... Opto Input 1,2,3,4,5,6,7 or 8
Reset Method ............................................................ LOCAL, LOCAL&REMOTE