RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
161
EN
HANCED
TEC
HNOLOGY
※
. NOTE :
RMT Func-GND, RMT Func-SEF and RMT Func-NEG, the same as RMT Func-
PHA above.
PRIMARY SETTING / PROTECTION / COLD LOAD PICKUP / CLPU-TYPE1 / Reset Time
Range
0.00 ~ 600.00 sec
Default
0.60
Step
0.01 sec
Select the cold load reset time required for the inrush load.
If the cold load currents drop below nominal pickup levels, the cold
load pickup feature is returned the normal sequence when the cold load
reset time expires.
CLPU-TYPE2 Setup
This setup is to rise or drop the current for Over Current Pickup of a protection element
PRIMARY SETTING / PROTECTION / COLD LOAD PICKUP / CLPU-TYPE2 / E-CLP Multi’
Range
0.0 (OFF),1.0~5.0
Default
2.0
Step
0.1
Set the multiple of cold load. If OFF is set, the cold load multiple is not
applied and the setting of minimum working current is always applied
for overcurrent pickup current.
PRIMARY SETTING / PROTECTION / COLD LOAD PICKUP / CLPU-TYPE2/ E-CLP Time
Range
1~720min
Default
10
Step
1
Set the cold load time. During this set time, the overcurrent pickup
level is risen or dropped.
[CLPU-TYPE2]
>
E-CLP Multi’: 2.0
>E-CLP Time(m): 10
[CLPU-TYPE2]
>E-CLP Multi’: 2.0
E-CLP Time(m): 10
[CLPU-TYPE1]
RMT Func-SEF: ON
RMT Func-NEQ: ON
>Reset Time: 0.60