RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
151
EN
HANCED
TEC
HNOLOGY
PRIMARY SETTING / PROTECTION / H/C LOCKOUT-GND / Time Delay
Range
0.00 ~ 10.00 sec
Default
0.00
Step
0.01 sec
The Time delay of phase high current trip setting programs a definite
time delay for the phase high current trip. If set to zero, phase high
current trip operates instantaneously.
PRIMARY SETTING / PROTECTION / H/C LOCKOUT-GND / Active Trip
Range
OFF, 1 ~ 5
Default
OFF
Step
1
If Active Trip = OFF,
the feature is not operate.
If Active Trip = 2,
then phase high current trip is enabled for the
second trip operation and every following trip operation.
[ H/C LOCKOUT-GND ]
Pickup(A): 8000
Time Delay: 0.00
>Active Trip: OFF
[ H/C LOCKOUT-GND ]
Relays(0-8): OFF
Pickup(A): 8000
>Time Delay: 0.00